Permit Information
Permit NumberFIR11-00399
StatusFinaled
Name ALARMCO
Site Address 12065 W MCMILLAN RD
Project NameFIRE STATION #10
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to provide a non-required manual system with performance-based automatic smoke detection. The system includes full notification, partial smoke detection, pull stations, and heat detectors. An AES RF Radio is being provided instead of the DACT with an IntelliTap. No HVAC has been shown on the plans. There is no associated building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  11/14/2011 DONE
Plans taken to records for scanning.
INSP-Final Inspection10/17/201110/17/201110/17/2011PPASS
DetailsTroy Cobbley
Permit finaled
Issue permit  10/13/2011 DONE
Payment received via Govolutions
Fees Due Hold10/13/2011 10/13/2011 DONE
Details
INSP-Final Inspection10/11/201110/12/201110/12/2011AFAIL
DetailsTroy Cobbley
Signals are now being reported correctly. As-builts/Intelipro information was not provided as requested by plan review.
Miscellaneous action  10/5/2011 DONE
I recieved and email from Lori at Alarmco asking if they could use an IntelliPro instead of an IntelliTap with the AES. I let her know that for this particular fire alarm panel, it is approved to use the AES-7794 IntelliPRO PROVIDED only the CID/Pulse format be used. I also asked her to please provide this information to the inspector for field verification.
INSP-Final Inspection9/30/20119/30/20119/30/2011PFAIL
DetailsTroy Cobbley
Tested the flow switch, tamper #1 and main lobby pull station. Paul received the signals from the relays but no informaton from the intela tap came in.
INSP-Final Inspection9/28/20119/28/20119/28/2011PFAIL
DetailsTroy Cobbley
Tamper #1 needs adjusted, could not find the inspectors test valve so the flow switch was not tested. Also need the tamper switch and manual pull stations addresses on the panel to match the map and what is reported to central station. All other items were tested. Horns did not sync but Gary fixed this while I waited.
INSP-Final Inspection9/26/20119/26/20119/26/2011PFAIL
DetailsTroy Cobbley
Did not perform the testing due to the intella tap not being installed on the AES dialer.
INSP-Final Inspection9/21/20119/22/20119/22/2011AFAIL
DetailsTroy Cobbley
See the city approved plans for locations of corrections needed. No actual testing was performed
CHANGE STATUS TO (ISS)  9/21/2011 DONE
DetailsTisha Gallop
Plan assigned to (Stephanie)9/12/2011 9/20/2011 DONE
DetailsStephanie L. Cobbley
Alarm Plan Check9/20/2011 9/20/2011 PASS
DetailsStephanie L. Cobbley
Plan modification approved with redlines and review comments.
PLANS TAKEN FRONT DESK ALARM  9/20/2011 DONE
Approved redlined plan modification documents available at front counter.
Inspection Record Card- Fire9/20/2011 9/20/2011 DONE
DetailsPatricia Smith
Telephone call  9/20/2011 DONE
t/c w lori - permit (plan mod) ready and fees given
Permit Ready to Issue  9/20/2011 DONE
Details
Miscellaneous action  9/19/2011 DONE
The contractor chose to provide a beam detector instead of the originally submitted heat detectors due to ceiling heights/peaks/beams causing problems with meeting spacing requirements. The beam detector was shown on the plans without any indications of roof-line details, ceiling heights, or beam placement (see 2009 IFC 907.1.2 #11). I decided to do a site visit to try and help the contractor with a solution to the detection problem. During that site visit, it was determined that the proposed beam detector location would not sufficiently cover the Rig Room area, and that a possible solution might be to move the beam detector and it’s receiver to the wall. However due to obstructions from fire trucks, mechanical ducting, and lighting fixtures, the wall location would not meet the listing of the device either. It was determined that the component could not be approved because it would not meet the specifications or purpose of the device. After explaining this to the contractor, Alarmco informed me that Mitch Caldwell decided that since detection is not required in this space, that there would be no detection provided in the Rig Room area.
Plan resubmittals received  9/15/2011 DONE
DetailsChristina Prado
Received two new sets of plans and specs
Plan resubmittals received  9/12/2011 DONE
DetailsTisha Gallop
Plan Modification: received two copies of application, folder and plans; routed to Fire review.
INSP-Conference8/31/20118/31/20118/31/2011PDONE
DetailsTroy Cobbley
Performed site visit to determine placement of heat detectors and found that the city approved plans do not show the heat detectors spaced for "sloped" ceilings, "High" ceilings or spacing taking "beam construction" into account. The plans also do not reflect the existing fire sprinkler riser which includes two interior tamper switches, an exterior wall PIV and a flow switch. After a discussion with plan review it was determined that a plan modification/resubmittal is needed to show this information. This was relayed to the fire alarm tech.
Issue and Print Permit  8/25/2011 DONE
DetailsBarbara Stitt
Plan assigned to (Stephanie)8/10/2011 8/22/2011 DONE
DetailsStephanie L. Cobbley
1st review completed  8/22/2011 DONE
Alarm Plan Check8/22/2011 8/22/2011 PASS
DetailsStephanie L. Cobbley
Approved with redlines and review comments.
PLANS TAKEN FRONT DESK ALARM  8/22/2011 DONE
Approved redlined plans available at front counter.
Inspection Record Card- Fire8/22/2011 8/22/2011 DONE
DetailsPatricia Smith
Telephone call  8/22/2011 DONE
t/c w lori - permit ready and fees given
Permit Ready to Issue  8/22/2011 DONE
Details
Application received  8/10/2011