INSP-Final Inspection | 10/31/2011 | 10/31/2011 | 10/31/2011 | P | PASS |
Troy Cobbley
|
|
|
The hood suppression system functioned correctly. Permit finaled.
|
INSP-Final Inspection | 10/26/2011 | 10/27/2011 | 10/27/2011 | A | FAIL |
Troy Cobbley
|
|
|
The pizza oven suppression system can be finaled when the paper work is signed. Per the IMC commentary this type of oven can be installed under a type II hood so the duct/plenum nozzles are adequate. The other supression system, when activated, did not turn off the under hood lights. So it will need to be retested once the wiring has been corrected.
|
Application received | | | 8/12/2011 | | |
|
|
|
|
Issue and Print Permit | | | 8/12/2011 | | DONE |
Barbara Stitt
|
|
|
|