INSP-Final Inspection | 8/22/2011 | 8/23/2011 | 8/23/2011 | A | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Sprinkler Rough-in | 8/19/2011 | 8/22/2011 | 8/22/2011 | A | PASS |
Troy Cobbley
|
|
|
Rough-in passed sprinkler piping is ok to cover
|
INSP-Sprinkler Rough-in | 8/19/2011 | 8/19/2011 | 8/19/2011 | P | CANC |
Forrest France
|
|
|
Overbooked
|
Issue and Print Permit | | | 8/18/2011 | | DONE |
Barbara Stitt
|
|
|
|
Plan assigned to (Tim) | 8/16/2011 | | 8/17/2011 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 8/17/2011 | | 8/17/2011 | | FAIL |
Tim Frost
|
|
|
Hydraulic calculations are required to substantiate the pipe sizing on the end two branch lines since they are side fed and not inside the grid.
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 8/17/2011 | | DONE |
Tim Frost
|
|
|
|
Telephone call | | | 8/17/2011 | | DONE |
|
|
|
left vm for greg - permit denied - needs to be picked up and resubmitted
|
Plan resubmittals received | | | 8/17/2011 | | DONE |
|
|
|
|
Sprinkler Plan Check | 8/17/2011 | | 8/17/2011 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/17/2011 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 8/17/2011 | | 8/17/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 8/17/2011 | | DONE |
|
|
|
t/c w greg - permit ready and fees given
|
Permit Ready to Issue | | | 8/17/2011 | | DONE |
|
|
|
|
Application received | | | 8/16/2011 | | |
|
|
|
|
Pending Assignment by SAM | 8/16/2011 | | 8/16/2011 | | DONE |
Patricia Smith
|
|
|
|