Permit Information
Permit NumberFIR11-00428
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 11311 W CHINDEN BLVD
Project NameHP BLDG 3-PHASE II CAFE' - SER
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to provide monitor modules for new hood suppression systems, relocate existing initiating and notification devices, and add new notification to accommodate a tenant remodel.

Associated building permit: BLD11-01344 (HEWLETT PACKARD) (PHASE II CAFE' - SERVERY REMODEL) Remodel to the existing dining / preparation assembly use cafeteria per approved plans. Work to include select interior demolition. Modification of existing kitchen area to become a large servery area for patrons to pass through selecting food and beverage choices before going to the seating areas. Modifications to the existing 1-hour roof/ceiling assembly (ESR-1222) and 1-hour occupancy separation wall separating the original A2.1 assembly dining / kitchen area accessory use area per the UBC under which remodels & upgrades were done, from the adjacent two story 'B' occupancy office building. Building 1, 2, 3, 5, & 7 of the Hewlet Packard campus are part of an unlimited area building as a 'B' occupancy use with 60 feet all around and fully sprinklered. The A2.1 dining / kitchen area was required to be of type II-1 hour construction and an accessory use to building three. All modifications to roof/ceiling assembly, penetrations and openings are to be such that the 1-hour construction is maintained. drs

Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  11/14/2011 DONE
Plans taken to records for scanning.
INSP-Final Inspection10/31/201110/31/201110/31/2011PPASS
DetailsTroy Cobbley
permit finaled.
INSP-Alarm Testing10/26/201110/27/201110/27/2011APASS
DetailsTroy Cobbley
permit finaled
INSP-Alarm Testing10/18/201110/18/201110/18/2011ADONE
DetailsTroy Cobbley
Todays inspection was a walk throught to verify device placement prior to actual testing. I found two strobes that are overspaced that will need to be relocated or have the candella increased. Also there is an existing manual pull station that is mounted above 48". I need verification that it met the code under which it was installed or it needs to be lowered.
INSP-Conference9/12/20119/12/20119/12/2011PDONE
DetailsForrest France
On site conference regarding conditions per IFC 904.11.1.
Override - Parcel Holds  9/6/2011  
Override - Parcel Holds  9/6/2011  
Issue and Print Permit  9/6/2011 DONE
Plan assigned to (Stephanie)8/22/2011 8/31/2011 DONE
DetailsStephanie L. Cobbley
1st review completed  8/31/2011 DONE
Alarm Plan Check8/31/2011 8/31/2011 PASS
DetailsStephanie L. Cobbley
Plans approved with redlines and review comments.
PLANS TAKEN FRONT DESK ALARM  8/31/2011 DONE
Approved redlined plans available at front counter.
Override - Parcel Holds  8/31/2011  
Override - Parcel Holds  8/31/2011  
Inspection Record Card- Fire8/31/2011 8/31/2011 DONE
DetailsPatricia Smith
Telephone call  8/31/2011 DONE
t/c w dante - permit ready and fees given
Override - Parcel Holds  8/31/2011  
Override - Parcel Holds  8/31/2011  
Permit Ready to Issue  8/31/2011 DONE
Details
Application received  8/22/2011