Miscellaneous action | | | 10/13/2011 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 9/13/2011 | 9/14/2011 | 9/14/2011 | A | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Final Inspection | 9/12/2011 | 9/13/2011 | 9/13/2011 | A | FAIL |
Troy Cobbley
|
|
|
Could not get the hvac unit to turn on. It actually started to smoke from the return intake. No testing was able to be performed. Re-inspection fee applied.
|
INSP-Final Inspection | 9/8/2011 | 9/9/2011 | 9/9/2011 | A | FAIL |
Forrest France
|
|
|
HVAC unit not functional to enable testing of the new duct smoke detector, also need to post updated points map at the RA, no access to the FACP room.
|
INSP-Final Inspection | 9/7/2011 | 9/7/2011 | 9/7/2011 | P | FAIL |
Troy Cobbley
|
|
|
The gas to the hvac unit has not been turned on so the smoke detector could not be tested.
|
INSP-Final Inspection | 9/2/2011 | 9/2/2011 | 9/2/2011 | P | CANC |
Troy Cobbley
|
|
|
Please call Gary at ###-#### with inspection time. Phone #: ###-#### >> Inspection requested via web by Lori Brungardt Inspection cancelled from web by: Lori Brungardt
|
Plan assigned to (Stephanie) | 8/23/2011 | | 8/25/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Plan assigned to (Stephanie) | 8/23/2011 | | 8/25/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Telephone call | | | 8/25/2011 | | DONE |
|
|
|
Spoke to Lori at Alarmco. The submitted one-line indicates there is an existing AES RF radio, however there is no record of a permit being pulled to install it. She said she would do some research to find out what happened and will call me back.
|
1st review completed | | | 8/25/2011 | | DONE |
|
|
|
|
Alarm Plan Check | 8/25/2011 | | 8/25/2011 | | PASS |
Stephanie L. Cobbley
|
|
|
Quick permit approved with redlines - no written review comments.
|
Miscellaneous action | | | 8/25/2011 | | DONE |
|
|
|
Lori with Alarmco let me know the correct FIR permit number the existing AES panel was installed under: FIR09-00174.
|
PLANS TAKEN FRONT DESK ALARM | | | 8/25/2011 | | DONE |
|
|
|
Approved quick permit plans are available at the front counter.
|
Inspection Record Card- Fire | 8/25/2011 | | 8/25/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 8/25/2011 | | DONE |
|
|
|
t/c w lori - permit ready and fees given
|
Permit Ready to Issue | | | 8/25/2011 | | DONE |
|
|
|
|
Issue and Print Permit | | | 8/25/2011 | | DONE |
Barbara Stitt
|
|
|
|
Application received | | | 8/23/2011 | | |
|
|
|
|