Miscellaneous action | | | 11/30/2012 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 10/16/2012 | 10/17/2012 | 10/17/2012 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 9/26/2012 | 9/27/2012 | 9/27/2012 | A | CANC |
Troy Cobbley
|
|
|
I spoke to Brian Giacomino about the plans needing to be resubmitted due to device change out and new NAC panel installation.
|
INSP-Final Inspection | 7/10/2012 | 7/10/2012 | 7/10/2012 | A | FAIL |
Troy Cobbley
|
|
|
Horns did not sync though it is better with the new changes. Horns shall sync per NFPA 72, 18.4.2.5 and per the Boise City Fire Dept.
|
INSP-Final Inspection | 6/27/2012 | 6/28/2012 | 6/28/2012 | A | FAIL |
Troy Cobbley
|
|
|
Per the acting fire marshal, Gordon Goldsmith, the horns and the strobes need to meet NFPA 72 requirements for syncronization prior to a final sign off for the fire alarm permits.
|
INSP-Conference | 4/13/2012 | 4/16/2012 | 4/16/2012 | A | DONE |
Troy Cobbley
|
|
|
Rob Ahten, kevin and I went over obstructions to the visual coverage. There are many cubicle walls that exceed 6' in height.
|
INSP-Final Inspection | 2/28/2012 | 2/28/2012 | 2/28/2012 | P | PART |
Forrest France
|
|
|
Final pending corrections per 430 completed 8/29/11 regarding sync issues.
|
INSP-Sprinkler Rough-in | 12/8/2011 | 12/9/2011 | 12/9/2011 | A | CANC |
Troy Cobbley
|
|
|
Wrong permit called in for inspection. The fire sprinkler was intended.
|
INSP-Final Inspection | 8/29/2011 | 8/29/2011 | 8/29/2011 | P | PART |
Troy Cobbley
|
|
|
Fire alarm functioned correctly. The issue is visual and audio sync'ing between the remodeled section and the existing area. Per Rob this issue is being worked on. Permit can be finaled when this is fixed and verified.
|
INSP-Final Inspection | 8/26/2011 | 8/26/2011 | 8/26/2011 | P | CANC |
Troy Cobbley
|
|
|
Inspection is going to be performed when the second half of phase 1 is reviewed, issued and installed.
|
INSP-Final Inspection | 8/26/2011 | 8/29/2011 | 8/26/2011 | A | CANC |
Troy Cobbley
|
|
|
Contact: Rafe - inspection must be done at 7:30 before opening please Phone #: ###-#### >> Inspection requested via web by Deb Gooden Inspection cancelled from web by: Deb Gooden
|
INSP-Final Inspection | 8/25/2011 | 8/26/2011 | 8/26/2011 | A | CANC |
Troy Cobbley
|
|
|
Contact: Rafe Phone #: ###-#### >> Inspection requested via web by Deb Gooden Inspection cancelled from web by: Deb Gooden
|
Inspection Record Card- Fire | 8/25/2011 | | 8/25/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 8/25/2011 | | DONE |
|
|
|
t/c w daric - permit ready and fees given
|
Permit Ready to Issue | | | 8/25/2011 | | DONE |
|
|
|
|
Issue and Print Permit | | | 8/25/2011 | | DONE |
Barbara Stitt
|
|
|
|
Application received | | | 8/24/2011 | | |
|
|
|
|
Plan assigned to (Stephanie) | 8/24/2011 | | 8/24/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Plan assigned to (Stephanie) | 8/24/2011 | | 8/24/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 8/24/2011 | | DONE |
|
|
|
|
Alarm Plan Check | 8/24/2011 | | 8/24/2011 | | PASS |
Stephanie L. Cobbley
|
|
|
Quick permit approved - no written review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 8/24/2011 | | DONE |
|
|
|
Approved quick permit documents available at front counter.
|