Permit Information
Permit NumberFIR11-00440
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 11311 W CHINDEN BLVD
Project NameHP BLDG 5-LEGAL FOCUS ROOMS
Customer Number 
ePlanReviewNo
Description
This quick permit is to provide two strobe only notification devices and tie them in to an existing circuit to accomodate a tenant remodel. Approval is subject to field measurement of the EOL voltage drop. For appliances with an operating voltage range of 16V – 33V, the minimum acceptable voltage is 19.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V. UL 864, Standard for Control Units for Fire Signaling Systems. The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector. There are no written review comments. Associated building permit: BLD11-01319 (HP BLDG 5 - LEGAL FOCUS ROOMS) Construct two offices about 100 sq/ft each using two existing walls adding two doors and about 40 ft of new wall,
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  11/14/2011 DONE
Plans taken to records for scanning.
INSP-Final Inspection11/3/201111/4/201111/4/2011APASS
DetailsTroy Cobbley
permit finaled
Miscellaneous action  11/3/2011 DONE
Contractor requested a copy of the City approved drawings because they lost the job site copy. I made the copy and took it to the front counter for the contractor to pick up.
Override - Parcel Holds  9/6/2011  
Override - Parcel Holds  9/6/2011  
Issue and Print Permit  9/6/2011 DONE
Plan assigned to (Stephanie)8/24/2011 8/25/2011 DONE
DetailsStephanie L. Cobbley
Plan assigned to (Stephanie)8/24/2011 8/25/2011 DONE
DetailsStephanie L. Cobbley
1st review completed  8/25/2011 DONE
Alarm Plan Check8/25/2011 8/25/2011 PASS
DetailsStephanie L. Cobbley
Quick permit approved - no written review comments.
PLANS TAKEN FRONT DESK ALARM  8/25/2011 DONE
Quick permit plans available at front counter.
Override - Parcel Holds  8/25/2011  
Override - Parcel Holds  8/25/2011  
Inspection Record Card- Fire8/25/2011 8/25/2011 DONE
DetailsPatricia Smith
Telephone call  8/25/2011 DONE
t/c w dante - permit ready and fees given
Override - Parcel Holds  8/25/2011  
Override - Parcel Holds  8/25/2011  
Permit Ready to Issue  8/25/2011 DONE
Details
Application received  8/24/2011