INSP-Final Inspection | 10/19/2011 | 10/20/2011 | 10/20/2011 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Sprinkler Rough-in | 10/13/2011 | 10/14/2011 | 10/14/2011 | A | PART |
Troy Cobbley
|
|
|
Sprinkler piping is ok to cover. The single pendant head located in the storage room is spaced at 9'-1" off of one wall. This exceeds the distance allowed for the small room rule plus this is a ordinary hazard area. This head will need to be relocated and can be verified at the final inspection.
|
INSP-Sprinkler Rough-in | 10/12/2011 | 10/13/2011 | 10/13/2011 | A | CANC |
Troy Cobbley
|
|
|
Overbooked. Will need to be rescheduled
|
INSP-Sprinkler Rough-in | 9/28/2011 | 9/29/2011 | 9/29/2011 | A | PASS |
Troy Cobbley
|
|
|
The entry area soffit sprinkler piping is ok to cover. I noted on the city approved plans where coverage is blocked by a header directly above/at the entry door.
|
Sprinkler Plan Check | 9/23/2011 | | 9/23/2011 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 9/23/2011 | | DONE |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/23/2011 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 9/23/2011 | | 9/23/2011 | | DONE |
Patricia Smith
|
|
|
|
Issue and Print Permit | | | 9/23/2011 | | DONE |
Barbara Stitt
|
|
|
|
Plan resubmittals received | | | 9/22/2011 | | DONE |
|
|
|
|
Issue and Print Permit | | | 9/8/2011 | | DONE |
|
|
|
|
Plan assigned to (Tim) | 9/6/2011 | | 9/7/2011 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 9/7/2011 | | 9/7/2011 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 9/7/2011 | | DONE |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/7/2011 | | DONE |
Tim Frost
|
|
|
|
Override - Parcel Holds | | | 9/7/2011 | | |
|
|
|
|
Inspection Record Card- Fire | 9/7/2011 | | 9/7/2011 | | DONE |
Barbara Stitt
|
|
|
|
Override - Parcel Holds | | | 9/7/2011 | | |
|
|
|
|
Permit Ready to Issue | | | 9/7/2011 | | DONE |
Barbara Stitt
|
|
|
|
Telephone call | | | 9/7/2011 | | DONE |
Barbara Stitt
|
|
|
Called Brodie and told him that permit is ready on 9-7-11 @ 8:30am//BAS
|
Application received | | | 9/6/2011 | | |
|
|
|
|
Pending Assignment by SAM | 9/6/2011 | | 9/6/2011 | | DONE |
Patricia Smith
|
|
|
|