Miscellaneous action | | | 12/16/2011 | | DONE |
Tim Frost
|
|
|
Sent to Records for scanning.
|
INSP-Final Inspection | 10/27/2011 | 10/27/2011 | 10/27/2011 | A | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Final Inspection | 10/7/2011 | 10/10/2011 | 10/10/2011 | P | FAIL |
Troy Cobbley
|
|
|
Project is not ready for a final inspection. See the city approved plans for locations where additional sprinkler piping is ok to cover marked with todays date.
|
INSP-Sprinkler Rough-in | 9/26/2011 | 9/26/2011 | 9/26/2011 | P | PASS |
Troy Cobbley
|
|
|
Four additional heads as marked on the plans are ok for cover.
|
INSP-Sprinkler Rough-in | 9/22/2011 | 9/22/2011 | 9/22/2011 | P | PASS |
Troy Cobbley
|
|
|
The sprinkler piping above the lay-in tile areas can be covered. Also the pendants marked "ok" in red in the hard lid areas are ok to cover
|
Plan assigned to (Tim) | 9/19/2011 | | 9/22/2011 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 9/22/2011 | | 9/22/2011 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 9/22/2011 | | DONE |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/22/2011 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 9/22/2011 | | 9/22/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 9/22/2011 | | DONE |
|
|
|
t/c w jeff - permit (plan mod) ready and fees given
|
Permit Ready to Issue | | | 9/22/2011 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 9/22/2011 | | DONE |
Christina Prado
|
|
|
|
Plan resubmittals received | | | 9/19/2011 | | |
|
|
|
|
INSP-Sprinkler Rough-in | 9/12/2011 | 9/12/2011 | 9/12/2011 | P | FAIL |
Troy Cobbley
|
|
|
Todays inspection was for the gridded area which failed due to the actual pendant head layout not matching the approved plans. This same area happens to be a remote area. Plans need to be resubmitted showing the actual layout and any hydraulic remote area modifications if needed.
|
Plan assigned to (Tim) | 9/6/2011 | | 9/8/2011 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 9/8/2011 | | 9/8/2011 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 9/8/2011 | | DONE |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/8/2011 | | DONE |
Tim Frost
|
|
|
|
Override - Parcel Holds | | | 9/8/2011 | | |
|
|
|
|
Override - Parcel Holds | | | 9/8/2011 | | |
|
|
|
|
Permit Ready to Issue | | | 9/8/2011 | | DONE |
Barbara Stitt
|
|
|
|
Override - Parcel Holds | | | 9/8/2011 | | |
|
|
|
|
Override - Parcel Holds | | | 9/8/2011 | | |
|
|
|
|
Inspection Record Card- Fire | 9/8/2011 | | 9/8/2011 | | DONE |
Barbara Stitt
|
|
|
|
Telephone call | | | 9/8/2011 | | DONE |
Barbara Stitt
|
|
|
Called and left a voise message that permit is ready & fees due on 9-8-11 @ 11:00am//BAS
|
Override - Parcel Holds | | | 9/8/2011 | | |
|
|
|
|
Override - Parcel Holds | | | 9/8/2011 | | |
|
|
|
|
Issue and Print Permit | | | 9/8/2011 | | DONE |
Tisha Gallop
|
|
|
|
Application received | | | 9/6/2011 | | |
|
|
|
|