Permit Information
Permit NumberFIR11-00482
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 10792 W FRANKLIN RD
Project NameIDAHO POWER OPERATIONS CENTER
Customer Number 
ePlanReviewNo
Description
This quick permit scope is to relocate three existing door holders and corresponding smoke detectors, delete two wall-mount horn/strobes, and provide three new ceiling mount horn/strobes. The new devices are to be tied in to the existing system. Approval is subject to field measurement of the EOL voltage drop. For appliances with an operating voltage range of 16V – 33V, the minimum acceptable voltage is 19.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V. UL 864, Standard for Control Units for Fire Signaling Systems. The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector. There are no written review comments. Associated building permit: BLD11-01371 (IDAHO POWER OPERATIONS CENTER – Vestibule and Conference room remodel) Permit is to remodel an existing conference room and an existing entry vestibule. This building is not fire sprinklered. Approval contingent upon adhering to the approved plans on file and plan review report. Work to include: construction of new interior non-bearing wall to create alcoves for existing doors and to define new vestibule, installation of new doors / accessible hardware, and finishes in compliance with chapter 8 of the 2009 IBC. This building is not Fire Sprinklered. **TLW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  1/20/2012 DONE
Plans taken to records for scanning.
INSP-Final Inspection12/28/20111/3/20121/3/2012APASS
DetailsTroy Cobbley
Permit finaled
INSP-Alarm Testing11/7/201111/9/201111/9/2011AFAIL
DetailsTroy Cobbley
The city approved plans are missing the second floor plan sheet. Also need the smoke detectors centered on the doors. This includes the first floor conference and second floor conference rooms.
Permit Ready to Issue  9/8/2011 DONE
DetailsBarbara Stitt
Inspection Record Card- Fire9/8/2011 9/8/2011 DONE
DetailsBarbara Stitt
Telephone call  9/8/2011 DONE
DetailsBarbara Stitt
Called Dante and told him that permit is ready & fees due on 9-8-11 @ 8:15am//BAS
Issue and Print Permit  9/8/2011 DONE
DetailsTisha Gallop
Application received  9/7/2011  
Plan assigned to (Stephanie)9/7/2011 9/7/2011 DONE
DetailsStephanie L. Cobbley
1st review completed  9/7/2011 DONE
Alarm Plan Check9/7/2011 9/7/2011 PASS
DetailsStephanie L. Cobbley
Quick permit approved - no written review comments.
PLANS TAKEN FRONT DESK ALARM  9/7/2011 DONE
Approved quick permit plans available at front counter.