Permit Information
Permit NumberFIR11-00491
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 1750 W FRONT ST
Project NameAlscott Grove St. Office Bldg
Customer Number 
ePlanReviewNo
Description
This quick permit is to provide three new notificaiton devices and connect them to the existing fire alarm system due to a tenant remodel. Approval is subject to field measurement of the EOL voltage drop. The voltage drop calculations are based on a 10% drop, therefore the minimum acceptable voltage is 21.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V. UL 864, Standard for Control Units for Fire Signaling Systems. The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector. There are no written review comments. Associated building permit: BLD11-01568 (WESTERN CAPITOL – Alscott Grove St. Office Bldg – 1st Floor) Permit to remodel an existing 5,349 square foot office space (occupied under BLD07-02501) by combining it with the adjacent 3,570 (Occupied under BLD01-01090) square foot office space creating a 8,919 square foot office space. This building is fully fire sprinklered. Scope of work includes: installation of new non bearing interior partition walls creating two new office areas and a storage room, demolition of interior nonbearing walls to combine the two spaces, installation of three exterior windows, installation of new sink in existing millwork, installation of new accessible doors / hardware, and interior finishes per Ch. 8 of the 2009 IBC. This building is fully Fire Sprinklered with an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **TLW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  10/13/2011 DONE
Plans taken to records for scanning.
INSP-Final Inspection9/21/20119/22/20119/22/2011APASS
DetailsForrest France
Scope of fire alarm work passed inspection. Permit final okay.
Issue and Print Permit  9/16/2011 DONE
DetailsBarbara Stitt
Inspection Record Card- Fire9/12/2011 9/12/2011 DONE
DetailsPatricia Smith
Telephone call  9/12/2011 DONE
t/c w earl - permit ready and fees given
Permit Ready to Issue  9/12/2011 DONE
Details
Application received  9/9/2011  
Plan assigned to (Stephanie)9/9/2011 9/9/2011 DONE
DetailsStephanie L. Cobbley
Plan assigned to (Stephanie)9/9/2011 9/9/2011 DONE
DetailsStephanie L. Cobbley
1st review completed  9/9/2011 DONE
Alarm Plan Check9/9/2011 9/9/2011 PASS
DetailsStephanie L. Cobbley
Quick permit approved - no written review comments.
PLANS TAKEN FRONT DESK ALARM  9/9/2011 DONE
Approved quick permit plans available at front counter.