Permit Information
Permit NumberFIR11-00498
StatusFinaled
Name ADVANCED FIRE & SAFETY
Site Address 8775 W USTICK RD
Project NameCole Community Church
Customer Number 
ePlanReviewNo
Description
Cole Community Church--Kitchen Fire Suppression System Renovation
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/28/20119/29/20119/29/2011APASS
DetailsTroy Cobbley
Permit finaled. The bulbs and the wiring have been removed from the lights under the hood.
INSP-Final Inspection9/26/20119/27/20119/27/2011AFAIL
DetailsTroy Cobbley
Everything functioned except the lights under the hood did not shut off when the system activated.
INSP-Supply line flush9/19/20119/20/20119/20/2011PFAIL
DetailsTroy Cobbley
The manual pull station is mounted too high, Also after a discussion it was fount that the exhaust fan does not stay on and the makeup air shut off when the the system activates. The lights under the hood also need to be verified that they shut off when the suppression system activates. No inspection was actually done.
Application received  9/12/2011  
Issue and Print Permit  9/12/2011 DONE