Miscellaneous action | | | 1/20/2012 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 11/30/2011 | 11/30/2011 | 11/30/2011 | P | PASS |
Forrest France
|
|
|
Scope of fire alarm permit work finaled. *Note: defficient items including missing smoke detection at leibert units, location of existing notification appliances and items 1 and 2 on the plan review are to remain at this time per building official J. Blais and fire chief R. Gervais.
*The existing switch gear room has been vacated and all electrical equipment and stationary storage batteries have been removed by the tenant. The clean agent fire protection and detection system has been removed under FIR11-00528. The existing fire/smoke rated wall assembly seperating the switch gear room and the mechanical room is no longer required and has been modified and subsequently no longer maintains an approved 1 hour rated assembly. The opening protection seperating the switch gear room and the mechanical room, (smoke dampers), may have been impaired due the removal of the area smoke detection required as part of the clean agent system removal. The mechanical division, building official, and fire code official have approved the 3 air handling units to remain as is, under the condition the space served by the air handling units remains unoccupied. An occupancy permit shall be obtained prior to untilization of the vacated space. *SJA*
|
INSP-Conference | 11/28/2011 | 11/28/2011 | 11/28/2011 | P | DONE |
Forrest France
|
|
|
|
INSP-Conference | 11/23/2011 | 11/23/2011 | 11/23/2011 | A | DONE |
Forrest France
|
|
|
On site meeting with contractor and mechanical inspectors regarding missing smoke detection at existing air handler units and conditions per IMC 2009 sec. 606.
|
INSP-Conference | 11/21/2011 | 11/21/2011 | 11/21/2011 | P | DONE |
Forrest France
|
|
|
Conversations with general and sub contractors regarding noted correction items.
|
INSP-Final Inspection | 11/14/2011 | 11/15/2011 | 11/15/2011 | A | FAIL |
Forrest France
|
|
|
See plan annotations for noted items including notification appliance coverage and location issues, missing SD at the three liebert units, batteries at the FACP, etc.
|
INSP-Final Inspection | 11/11/2011 | 11/14/2011 | 11/14/2011 | P | CANC |
Forrest France
|
|
|
Call Randy Phone #: ###-#### >> Inspection requested via web by Mike Brown Inspection cancelled from web by: Mike Brown
|
INSP-Final Inspection | 11/9/2011 | 11/10/2011 | 11/10/2011 | P | FAIL |
Troy Cobbley
|
|
|
Arrived at the job site but Randy called me to let me know there would be no access due to the property manager being in Gerome. No inspection was performed.
|
CHANGE STATUS TO (ISS) | | | 10/27/2011 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 10/24/2011 | | 10/24/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 10/24/2011 | | DONE |
|
|
|
t/c w ken - permit (plan mod) ready and fees given
|
Permit Ready to Issue | | | 10/24/2011 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 10/18/2011 | | 10/20/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | 10/20/2011 | | 10/20/2011 | | PASS |
Stephanie L. Cobbley
|
|
|
Plan modification approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 10/20/2011 | | DONE |
|
|
|
Approved, redlined plan modification documents available at front counter.
|
Telephone call | | | 10/20/2011 | | DONE |
|
|
|
t/c w ken - let him know that I could not process this permit until the past due fees were paid - he said he would take care of it
|
Plan resubmittals received | | | 10/18/2011 | | DONE |
Tisha Gallop
|
|
|
Plan Modification: Received two copies of application, submittal folder and plans; routed to Stephanie Cobbley.
|
INSP-Alarm Testing | 10/7/2011 | 10/10/2011 | 10/10/2011 | P | CANC |
Troy Cobbley
|
|
|
Per Jason this project is not quite ready for a final inspection. It will be rescheduled.
|
INSP-Alarm Testing | 10/7/2011 | 10/10/2011 | 10/7/2011 | P | CANC |
Forrest France
|
|
|
The phone number is Dave Dilley. Phone #: ###-#### >> Inspection requested via web by Mike Brown Inspection cancelled from web by: Mike Brown
|
Plan assigned to (Stephanie) | 9/26/2011 | | 10/4/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 10/4/2011 | | DONE |
|
|
|
|
Alarm Plan Check | 10/4/2011 | | 10/4/2011 | | PASS |
Stephanie L. Cobbley
|
|
|
Plans approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 10/4/2011 | | DONE |
|
|
|
Approved redlined plans available at front counter.
|
Inspection Record Card- Fire | 10/4/2011 | | 10/4/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 10/4/2011 | | DONE |
|
|
|
left vm for ken - permit ready and fees given
|
Permit Ready to Issue | | | 10/4/2011 | | DONE |
|
|
|
|
Issue and Print Permit | | | 10/4/2011 | | DONE |
Barbara Stitt
|
|
|
|
Application received | | | 9/26/2011 | | DONE |
Barbara Stitt
|
|
|
|