Miscellaneous action | | | 1/20/2012 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 11/14/2011 | 11/14/2011 | 11/14/2011 | P | PASS |
Forrest France
|
|
|
Fire alarm permit finaled. Inspection passed.
|
Issue and Print Permit | | | 10/14/2011 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 9/26/2011 | | 10/5/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 10/5/2011 | | DONE |
|
|
|
|
Alarm Plan Check | 10/5/2011 | | 10/5/2011 | | PASS |
Stephanie L. Cobbley
|
|
|
Plans approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 10/5/2011 | | DONE |
|
|
|
Approved redlined plans available at front counter.
|
Inspection Record Card- Fire | 10/5/2011 | | 10/5/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 10/5/2011 | | DONE |
|
|
|
left vm - permit ready and fees given
|
Permit Ready to Issue | | | 10/5/2011 | | DONE |
|
|
|
|
Application received | | | 9/26/2011 | | |
|
|
|
|