Miscellaneous action | | | 1/20/2012 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 1/3/2012 | 1/3/2012 | 1/3/2012 | A | PASS |
Forrest France
|
|
|
Fire alarm permit finaled.
|
INSP-Alarm Testing | 12/30/2011 | 1/3/2012 | 1/3/2012 | A | PASS |
Forrest France
|
|
|
Verified plan modification, reinspection completed. Contractor to provide points map at the panel indicating location of the yard PIV as discussed.
|
CHANGE STATUS TO (ISS) | | | 12/29/2011 | | DONE |
Tisha Gallop
|
|
|
|
Plan assigned to (Stephanie) | 12/22/2011 | | 12/28/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | 12/28/2011 | | 12/28/2011 | | PASS |
Stephanie L. Cobbley
|
|
|
Plan modification approved with review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 12/28/2011 | | DONE |
|
|
|
Approved plan modification documents available at front counter.
|
Inspection Record Card- Fire | 12/28/2011 | | 12/28/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 12/28/2011 | | DONE |
|
|
|
left vm for sean - permit (plan mod) ready and fees given
|
Permit Ready to Issue | | | 12/28/2011 | | DONE |
|
|
|
|
INSP-Final Inspection | 12/22/2011 | 12/23/2011 | 12/23/2011 | A | NR |
Forrest France
|
|
|
Fire alarm permit status "under review". Temp. occupancy approved per R. Gervais and based on field inspection completed 12/22.
|
INSP-Final Inspection | 12/22/2011 | 12/22/2011 | 12/22/2011 | P | NR |
Forrest France
|
|
|
|
INSP-Alarm Testing | 12/21/2011 | 12/22/2011 | 12/22/2011 | A | FAIL |
Forrest France
|
|
|
Yard post indicator tamper switch reported as a trouble open circut, plans do not match installation- noted five tamper switches and two flow switches have been added due to a PIV, antifreeze loop and DCVA not shown on plans, FACP has been relocated, floor control valves are now located in the riser room. Waterflow switch/outside bell repaired while on site. An approved plan modification will be necessary.
|
Plan resubmittals received | | | 12/22/2011 | | DONE |
Tisha Gallop
|
|
|
PLAN MODIFICATION: received application two submittal folders and plan sheets; routed to Steph.
|
INSP-Sprinkler Rough-in/Hydro | 12/19/2011 | 12/20/2011 | 12/20/2011 | P | CANC |
Forrest France
|
|
|
Toby Phone #: ###-#### >> Inspection requested via web by Sean DeLacy Inspection cancelled from web by: Sean DeLacy
|
Issue and Print Permit | | | 10/21/2011 | | DONE |
Barbara Stitt
|
|
|
|
Plan assigned to (Stephanie) | 9/27/2011 | | 10/5/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 10/5/2011 | | DONE |
|
|
|
|
Alarm Plan Check | 10/5/2011 | | 10/5/2011 | | PASS |
Stephanie L. Cobbley
|
|
|
Plans approved with review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 10/5/2011 | | DONE |
|
|
|
Approved plans available at front counter.
|
Inspection Record Card- Fire | 10/5/2011 | | 10/5/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 10/5/2011 | | DONE |
|
|
|
t/c w sean - permit ready and fees given
|
Permit Ready to Issue | | | 10/5/2011 | | DONE |
|
|
|
|
Application received | | | 9/27/2011 | | |
|
|
|
|