Permit Information
Permit NumberFIR11-00557
StatusFinaled
Name AUDIO ELECTRONICS INC
Site Address 625 W IDAHO ST
Project NameBOISE CITY HALL – HR DEPT REMO
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to modify the existing fire alarm system to accommodate a tenant remodel. This permit scope of work includes relocating a pull station, removing existing notification and replacing with new (to meet temporal code requirements), adding a remote power supply to accommodate the new notification devices, adding five new duct detectors, and a relay to release a magnetic door on general alarm.

Associated building permit: BLD11-01058 (CITY OF BOISE – 1st Floor – Human Resources) Permit is to remodel existing 2,340 square foot office area previously occupied by IT. Approval per approved plans on file. Work to include: [installation / demolition of interior partition walls to create a reception area, five new offices, a conference room, a file room, and open office area], new lighting, and interior finishes in compliance with chapter 8 of the 2006 IBC. This building is fully fire sprinklered any alterations or modifications to the sprinkler system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA #13 as regulated by the fire department. **TLW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  1/20/2012 DONE
Plans taken to records for scanning.
INSP-Final Inspection11/9/201111/9/201111/9/2011APASS
DetailsForrest France
Scope of fire alarm work passed functional testing. As-builts for field modifications recieved. Permit finaled.
Meeting  10/19/2011 DONE
Met with Jason with AEI regarding the audibility in existing vs. remodeled areas. Jason had questions about the requirements for conflicting audible notification. I explained that any area open to the t.i. space (i.e. not closed of by doors, walls, etc.) would need to match the new temporal code; while existing devices separated by rated walls etc could maintain the steady tone until those areas are upgraded provided the sounds are not obvious conflicts. I told Jason that once the new devices were in place, if they have questions during testing they could call in a conference and have the inspector come out to clarify any questions or issues that come up. While I was there, Jason asked if the existing pull stations would need to be relocated because they seemed too high. I told him it would depend on when those devices were installed and under what code they were approved. I let him know I would look in to it and call him. I said as long as the existing devices meet the code they were installed under and are not being modified in any way (i.e. relocated, replaced, etc...) then they could remain as-is.
Telephone call  10/19/2011 DONE
I called Jason regarding the questions about the existing pull station location. The HR installation of those pull stations was approved under the 1994 UFC that stated "manual pull stations shall be mounted no less than 3.5' to the bottom of the box and no greater than 5' to the top of the box". I told Jason as long as the existing pull stations fell under that range and as long as he's not modifying the devices, they could remain as-is.
Issue and Print Permit  10/17/2011 DONE
Inspection Record Card- Fire10/14/2011 10/14/2011 DONE
DetailsPatricia Smith
Telephone call  10/14/2011 DONE
t/c w lisa - permit ready and fees given
Permit Ready to Issue  10/14/2011 DONE
Details
Plan assigned to (Stephanie)10/12/2011 10/13/2011 DONE
DetailsStephanie L. Cobbley
1st review completed  10/13/2011 DONE
Alarm Plan Check10/13/2011 10/13/2011 PASS
DetailsStephanie L. Cobbley
Plans approved with redlines and review comments.
PLANS TAKEN FRONT DESK ALARM  10/13/2011 DONE
Approved redlined plans available at front counter.
Application received  10/12/2011