Miscellaneous action | | | 12/26/2012 | | DONE |
|
|
|
plans taken to records for scanning.
|
INSP-Final Inspection | 12/17/2012 | 12/18/2012 | 12/18/2012 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled.
|
INSP-Conference | 12/14/2012 | 12/17/2012 | 12/17/2012 | A | DONE |
Troy Cobbley
|
|
|
Project has been scheduled for a final
|
INSP-Conference | 12/14/2012 | 12/14/2012 | 12/14/2012 | P | DONE |
Troy Cobbley
|
|
|
I spoke to Deb again and she stated that she had spoken to Protex and that the final inspection should be getting scheduled for monday. I scheduled a follow up inspection.
|
INSP-Final Inspection | 10/9/2012 | 10/11/2012 | 10/12/2012 | A | FAIL |
Forrest France
|
|
|
Correction items are incomplete- SD at the panel missing, permit address is inaccurate, autotest trouble on the FACP, and the monitor module for the DSC power supply reported as a supervisory condition.
|
FIR-Aging Inspection | 9/11/2012 | 9/11/2012 | 9/12/2012 | | NR |
Troy Cobbley
|
|
|
I spoke with Deb again about the job status. She was going to talk to Rob with Protex about the job status.
|
FIR-Aging Inspection | 5/1/2012 | 5/1/2012 | 5/2/2012 | | NR |
Troy Cobbley
|
|
|
Deb with Tri-State is going to follow up on job status.
|
INSP-Final Inspection | 11/17/2011 | 11/18/2011 | 11/18/2011 | A | FAIL |
Troy Cobbley
|
|
|
Provide the correct building address, re-install the smoke detector over the facp and provide the AC power monitoring as per the installation guide for the DSC
|
Issue and Print Permit | | | 10/21/2011 | | DONE |
Barbara Stitt
|
|
|
|
Plan assigned to (Stephanie) | 10/12/2011 | | 10/14/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 10/14/2011 | | DONE |
|
|
|
|
Alarm Plan Check | 10/14/2011 | | 10/14/2011 | | PASS |
Stephanie L. Cobbley
|
|
|
Approved with review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 10/14/2011 | | DONE |
|
|
|
Approved plans available at front counter.
|
Inspection Record Card- Fire | 10/14/2011 | | 10/14/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 10/14/2011 | | DONE |
|
|
|
t/c w andrew - permit ready and fees given
|
Permit Ready to Issue | | | 10/14/2011 | | DONE |
|
|
|
|
Application received | | | 10/12/2011 | | |
|
|
|
|