Miscellaneous action | | | 6/1/2012 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 5/7/2012 | 5/7/2012 | 5/7/2012 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 5/2/2012 | 5/3/2012 | 5/3/2012 | P | NH |
Forrest France
|
|
|
Please call Randy 15-20 minutes prior to inspection. Thanks Phone #: ###-#### >> Inspection requested via web by Mark Sessions ** Arrived on site and met contractor, no access could be provided to complete a re-inspection **
|
INSP-Final Inspection | 4/6/2012 | 4/9/2012 | 4/9/2012 | A | FAIL |
Forrest France
|
|
|
Correction items include; relocate one SD, post map at the panel, provide smoke detection at the AES, provide knox box. See review note items 16, 32, and 33 for details. Location of the AES is not indicated on the plans.
|
INSP-Final Inspection | 4/4/2012 | 4/5/2012 | 4/5/2012 | A | CANC |
Troy Cobbley
|
|
|
Cancel per Randy since the monitoring information has not been set up.
|
Issue and Print Permit | | | 10/27/2011 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 10/19/2011 | | 10/25/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 10/25/2011 | | DONE |
|
|
|
|
Telephone call | | | 10/25/2011 | | DONE |
|
|
|
Spoke to Joe at Allied General and requested data sheets for the AES panel and IntelliTap. I let him know that the drawings were conflicting in battery type and other areas with circuiting. He asked if I needed new drawings and calcs. I told him I would just redline the plans and make them field verify, but that as-built drawings would be required unless other field changes require a plan modification.
|
Alarm Plan Check | 10/25/2011 | | 10/25/2011 | | PASS |
Stephanie L. Cobbley
|
|
|
Approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 10/25/2011 | | DONE |
|
|
|
Approved redlined plans available at front counter.
|
Inspection Record Card- Fire | 10/25/2011 | | 10/25/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 10/25/2011 | | DONE |
|
|
|
left vm for ken - permit ready and fees given
|
Permit Ready to Issue | | | 10/25/2011 | | DONE |
|
|
|
|
Application received | | | 10/19/2011 | | |
|
|
|
|