Permit Information
Permit NumberFIR11-00579
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 2667 S VICTORY VIEW WAY
Project NameD & A COMPANIES
Customer Number 
ePlanReviewNo
Description
The Fire Sprinkler Scope of work consists of a new two-story office warehouse. The new 6” underground under a separate permit supplies a 6” wall piv, 6” backflow preventer, 6” header, one 4” and two 2½” floor control valves. One of which is a (2½”) dry system for the loading dock. The warehouse portion is a 4”x4”x2” grid. The office area is a tree with 2½” and 2” mains with telescoping branch piping. The partial second floor has a 2½” main with telescoping branch piping. EC17 sprinklers are being utilized for the warehouse area based on 144 Sqft., 15’ maximum and 8’ minimum spacing.

Fire Prevention Officer and Fire Inspector
Based on the owner’s certificate and combustible storage form the storage does not have plastics except for 1-2 pallets of EPDM gaskets less than 5’ high and is less than 25% by volume plastic. (Please, see Fire Sprinkler Design and Spacing below.) There is no idle pallet storage. If the storage should change and no longer correlates with this information, please take appropriate action.

Contractor’s Note: The building permit has not been issued at this time. The building department may determine that changes are required to the building plans in order to meet code. These changes may affect the sprinkler system. The sprinkler contractor will be required to make all necessary changes that may be required. Therefore, if the sprinkler contractor chooses to proceed without an issued building permit they will do so on their own cognizance.

Underground was permitted under FIR11-00374


Building Department Scope:

D & A Glass - (FOUNDATION PERMIT) - This permit is issued to do site grading and drainage, to pour footings and foundation and do underground utilities for the future construction of the new D & A Glass Company two story bulding. Work under this permit shall not proceed beyond the pour of the foundation until final approval of plans and issuance of the full building permit. The building will be constructed under permit BLD11-00946. As owner or designated agent, I acknowledge that I am performing this work at my own risk without assurance that the permit for the entire building structure will be granted, and I agree to make any modifications to the early foundation work performed as may be required to comply with the City Codes and the final approved building plans and conditions. All per engineered plans on file.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  4/24/2012 DONE
DetailsTim Frost
Sent to Records for scanning.
INSP-Final Inspection1/3/20121/4/20121/4/2012APASS
DetailsTroy Cobbley
permit finaled
INSP-Sprinkler Rough-in/Hydro12/19/201112/20/201112/20/2011PPASS
DetailsTroy Cobbley
24 hour air test and forward flush passed. First floor office area piping can be covered.
INSP-Sprinkler Rough-in/Hydro12/19/201112/19/201112/19/2011PPASS
DetailsTroy Cobbley
Wet and dry system hydro tests passed. The 24 hour air test was started at 2:00 with 42psi on the guage.
INSP-Sprinkler Rough-in/Hydro12/15/201112/16/201112/16/2011APASS
DetailsTroy Cobbley
The rough-in inspection for all piping except for the first floor office area is passed. Mike needs to fix two retaining straps and provide flexible coupling at the top of all of the riser nipples. as shown on the approved plans. The piping in the dock area can be covered.
INSP-Sprinkler Rough-in/Hydro12/15/201112/15/201112/15/2011PCANC
DetailsTroy Cobbley
canceled due to time constraints
INSP-Sprinkler Rough-in12/8/201112/8/201112/8/2011PPASS
DetailsTroy Cobbley
The second floor office sprinkler piping can be covered.
INSP-Sprinkler Rough-in11/14/201111/15/201111/15/2011APASS
DetailsTroy Cobbley
First and second floor hard lid areas are ok to cover. I noted that the sprinkler protection provided over the main entry canopy has not been installed. Mike is going to have his office contact me on this.
INSP-Sprinkler Rough-in11/9/201111/9/201111/9/2011PPASS
DetailsTroy Cobbley
The piping above the mens and womens 2nd floor restrooms is ok to cover.
Issue and Print Permit  11/9/2011 DONE
DetailsBarbara Stitt
Plan assigned to (Tim)10/20/2011 11/8/2011 DONE
DetailsTim Frost
Sprinkler Plan Check11/8/2011 11/8/2011 PASS
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
PLANS/APPL TAKEN TO FRONT DESK  11/8/2011 DONE
DetailsTim Frost
Inspection Record Card- Fire11/8/2011 11/8/2011 DONE
DetailsPatricia Smith
Telephone call  11/8/2011 DONE
t/c w brad - permit ready and fees given
Permit Ready to Issue  11/8/2011 DONE
Details
Plan resubmittals received  11/4/2011 DONE
DetailsTisha Gallop
received application and three copies of submittal binder and plans; routed to Fire Review.
Sprinkler Plan Check10/27/2011 10/27/2011 FAIL
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
1st review completed  10/27/2011 DONE
DetailsTim Frost
Telephone call  10/27/2011 DONE
left vm for brad - permit denied - needs to be picked up and resubmitted
Miscellaneous action  10/21/2011 DONE
Sent combustible storage form to Brad for completion.
Application received  10/20/2011  
Case Summary  10/20/2011 DONE