INSP-Final Inspection | 3/8/2012 | 3/8/2012 | 3/9/2012 | A | PASS |
Forrest France
|
|
|
Per signed record of completion document dated 1/3/12, scope of fire alarm work passed field inspection by F. France. Permit final approved.
|
INSP-Final Inspection | 3/6/2012 | 3/7/2012 | 3/7/2012 | A | NR |
Forrest France
|
|
|
Check status Phone #: ###-#### >> Inspection requested via web by Jeff Walton
|
Fees Due Hold | 12/13/2011 | | 1/3/2012 | | DONE |
Patricia Smith
|
|
|
|
Alarm Plan Check | 12/12/2011 | | 12/12/2011 | | PASS |
Stephanie L. Cobbley
|
|
|
Plans approved per onsite plan review by T. Cobbley
|
PLANS TAKEN FRONT DESK ALARM | | | 12/12/2011 | | DONE |
|
|
|
|
Issue and Print Permit | | | 12/12/2011 | | DONE |
|
|
|
|
1st review completed | | | 12/8/2011 | | DONE |
|
|
|
|
Alarm Plan Check | 12/8/2011 | | 12/8/2011 | | FAIL |
Stephanie L. Cobbley
|
|
|
Failed per on-site plan review by T. Cobbley - the two new 30cd strobes on either side of the new tool need to be 75cd to provide coverage in the pathway around the new tool since the 30cd's will be overspaced.
|
Application received | | | 11/9/2011 | | DONE |
Mary Froemke
|
|
|
This permit was created on the web by Paul Marcolina
|
Application received | | | 11/9/2011 | | DONE |
|
|
|
This permit was created on the web by Paul Marcolina
|