Information based on query as of Thursday, September 10, 2026.
Permit Information
Permit NumberFIR11-00603
StatusFinaled
Name DOHERTY ELECTRIC
Site Address 927 W MYRTLE ST
Project NameINTERMOUNTAIN MEDICAL IMAGING
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to provide notification, remove existing duct detectors, relocate a pull station, remove an existing remote power supply and re-circuit all existing devices to the existing FACP to accommodate a tenant remodel. Some existing smoke detectors and notification devices are being relocated. Devices are to be connected to existing circuits. The existing remote annunciator panel is being relocated due to the remodel of the vestibule area.

Associated building permit: BLD11-02020 (INTERMOUNTAIN MEDICAL IMAGING - ADDITION AND REMODEL) (DRH11-00158) This building has a fire sprinkler system. To construct a 312 square foot 1 story addition on the West end of an existing 6,518 square foot building and to construct a new 102 square foot canopy next to the addition. After the addition and canopy, this building will have a total floor area of about 6,932 square feet. The interior of the building will also be remodeled. For the addition, work is to include concrete footings, concrete foundations, 2x8 LSL stud walls, wood shear walls, TJI roof joists, wood roof deck, foam plastic roof insulation, and a single ply membrane roof covering. For the remodel, work is to include concrete footings, steel columns, steel beams, interior nonbearing walls, a new MRI with supporting equipment and shielding, a dressing room accessible to the disabled, millwork, and finishes. All 4 restrooms are required to be maintained accessible to the disabled. Epoxy anchors, expansion anchors, welding, high-strength bolts, and the Exterior Insulation and Finish System (EIFS) all require Special Inspection. Permit BLD11-02202 was issued to enlarge an opening in the East wall and permit BLD11-02365 was issued to perform interior nonstructural demolition. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  9/27/2012 DONE
plans taken to records for scanning
INSP-Final Inspection6/25/20126/28/20126/28/2012APASS
DetailsForrest France
Completed fire alarm permit work acceptance test. Adjustments finished while on site.
INSP-Final Inspection6/25/20126/27/20126/25/2012ACANC
DetailsForrest France
We would like to meet you for an inspection at 7am if possible. Protex is the Fire Alarm Vendor their number is ###-#### (Rob Athen Cell) or office is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates Inspection cancelled from web by: Shawna Gates
FIR-Aging Inspection6/21/20126/21/20126/21/2012 DONE
DetailsForrest France
Work in progress, construction and finishes underway.
INSP-Alarm Testing2/16/20122/16/20122/16/2012APART
DetailsForrest France
Regarding occupant notification at the blood draw area.
Issue and Print Permit  12/5/2011 DONE
Inspection Record Card- Fire11/22/2011 11/22/2011 DONE
DetailsPatricia Smith
Telephone call  11/22/2011 DONE
t/c w mike - permit ready and fees given
Permit Ready to Issue  11/22/2011 DONE
Details
Alarm Plan Check11/21/2011 11/21/2011 PASS
DetailsStephanie L. Cobbley
Plans approved with redlines and review comments.
PLANS TAKEN FRONT DESK ALARM  11/21/2011 DONE
Approved redlined plans available at front counter.
Plan assigned to (Stephanie)11/10/2011 11/21/2011 DONE
DetailsStephanie L. Cobbley
Telephone call  11/17/2011 DONE
Left a message for the fire alarm vendor and the designer regarding major discrepencies between the submittals and the record drawings found in onbase under FIR99-00030.
Telephone call  11/17/2011 DONE
Spoke to Jared Miller at DC Engineering regarding the discrepencies between the record drawings and the recently submitted drawings as well as questions about the new smoke detectors being added (i.e. their purpose). He stated that he was not the designer of record but would get the information to the right person and have him/her call me. I emailed Jared the pdf files of the record drawings from FIR99-00030 (obtained from on-base)
Telephone call  11/17/2011 DONE
Rob A. with Protex returned my call to go over the discrepencies. He said that the record drawings we have are not how the system was actually installed. He stated that the SLC is class 'B' (not 'A' as the record drawings indicate). He said they are removing the remote power supply and putting all of the notification on the main FACP. Rob also stated that, per the mechanical engineer, the duct detectors are not required, therefore they are being removed as well. Rob verified that there is only one remote annunciator panel and it will be relocated to the new vestibule/entrance. Rob did not know the intent of the non-required new smoke detectors and stated that would need to be answered by the engineer/designer.
Telephone call  11/17/2011 DONE
Spoke with Rick at DC Engineering who verified what the vendor stated regarding the class A vs class B circuiting, removing the remote power supply, and only one remote annunciator panel. He stated that the smoke detectors were placed due to the IFC requirement in 907.2.2.1 for ambulatory health care facilities. I let him know that the building does qualify for the exception that states the automatic detection is not required if the building is equiped throughout with a sprinkler system. I let him know that if he would like to take the exception I could just make it a note on the plans and get them approved. However, if he chooses to keep the detection, I went over several areas that do not have adequate smoke detection coverage and let him know that I would then need to deny the plans and await a resubmittal providing additional devices and coverage. He said he would try to get back to me later today on a decision.
Plan resubmittals received  11/15/2011 DONE
DetailsTisha Gallop
received application and two copies of submittal folder and plans; routed to Fire Review.
1st review completed  11/14/2011 DONE
Alarm Plan Check11/14/2011 11/14/2011 FAIL
DetailsStephanie L. Cobbley
Plans denied - walls are missing and cannot verify spacing of devices.
Miscellaneous action  11/14/2011 DONE
Review comments faxed to the applicant.
Telephone call  11/14/2011 DONE
Called Rob to let him know the plans were being denied.
Miscellaneous action  11/14/2011 DONE
Denied plans available at front counter for contractor to pick up.
Application received  11/10/2011