Permit Information
Permit NumberFIR11-00642
StatusFinaled
Name MOUNTAIN POWER ELECT
Site Address 7009 W FRANKLIN RD
Project NameBISHOP KELLY H.S. – ADMIN/MAIN
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to remove, add, and/or relocate initiating and notification devices to accommodate the tenant remodel. A new NAC panel is being provided to tie in the new notification devices. New initiating devices are to be tied in to the existing SLC on the main FACP. Door holders and the remote annunciator are also being relocated due to the remodel. Initiating devices affected are duct detectors, smoke detectors, pull stations, and addressable monitor modules. Under a previous fire alarm permit (FIR11-00309) the existing FACP, VOIC1, and NAC1 panels were temporarily placed outdoors, however are being relocated to a storage room under this permit.

Associated building permit: BLD11-00836 Bishop Kelly High School - Administration and Main Entry Remodel and Addition - To demolish and remove approximately 7,100 square feet of existing building that contains administrative offices and a storage garage area. To reconstructed that portion of the building to contain reconfigured administrative offices and accessible restrooms and to constructed a 5,375 square foot addition that will contain a new main entry, lobby/study area, waiting area, new student commons and new men’s and women’s accessible restrooms. This permit also includes the construction of a new exterior entry plaza and other associate site improvements. This addition and remodel is being done on the northwest side of the high school. All construction per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  4/12/2012 DONE
Plans taken to records for scanning
INSP-Final Inspection2/15/20122/16/20122/16/2012APASS
DetailsTroy Cobbley
permti finaled
INSP-Final Inspection2/14/20122/14/20122/16/2012PPART
DetailsForrest France
Completed notification testing and EOL voltage measurements for new nac's at the remodel area. Noted one non-functional strobe at the SRO office, remainder of test passed.
INSP-Final Inspection2/15/20122/15/20122/15/2012PFAIL
DetailsTroy Cobbley
Everything is complete except that to final the project I need the requested alarm report for monday and tuesday. Inspection rescheduled for tomorrow morning per conversation with CM company.
INSP-Final Inspection2/13/20122/14/20122/14/2012AFAIL
DetailsTroy Cobbley
The corrections I had red lined have been addressed and the duct smoke detectors tested. As-builts will be needed showing the correct hvac unit/detector. Need the NAC circuits tested, sprinkler flow switches tested, a print out of the signals tested and final paper work for a final sign off.
INSP-Final Inspection2/10/20122/13/20122/13/2012PFAIL
DetailsTroy Cobbley
Todays inspection covered the new NAC panel and its interconnection with the existing FACP the testing of the new smoke detectors in Corridor 222 and the fire sprinkler riser tamper switches. The location of the inspectors tests were not immediately known. Heights and spacing of all of the new audio/visuals was also performed. I found several locations wheres a/v's were missing, a/v's overspaced and manual pull stations missing. The duct smoke detectors and NAC circuit testing was not performed. I spoke to Chad with Bishop Kelly about signage on the FACP room door and the fire sprinkler riser room door. I spoke to Colton about as-builts showing the door holder being deleted in Corridor 222.
INSP-Conference2/1/20122/1/20122/1/2012PDONE
DetailsTroy Cobbley
I went over duct smoke detector placement with Mountain Power Electric.
Plan assigned to (Stephanie)11/30/2011 12/7/2011 DONE
DetailsStephanie L. Cobbley
1st review completed  12/7/2011 DONE
Alarm Plan Check12/7/2011 12/7/2011 PASS
DetailsStephanie L. Cobbley
Approved with redlines and review comments.
PLANS TAKEN FRONT DESK ALARM  12/7/2011 DONE
Approved redlined plans available at front counter.
Inspection Record Card- Fire12/7/2011 12/7/2011 DONE
DetailsPatricia Smith
Telephone call  12/7/2011 DONE
t/c w kevin - permit ready and fees given
Permit Ready to Issue  12/7/2011 DONE
Details
Issue and Print Permit  12/7/2011 DONE
DetailsBarbara Stitt
Application received  11/30/2011