Miscellaneous action | | | 4/12/2012 | | DONE |
|
|
|
Plans taken to records for scanning
|
INSP-Final Inspection | 2/15/2012 | 2/16/2012 | 2/16/2012 | A | PASS |
Troy Cobbley
|
|
|
permti finaled
|
INSP-Final Inspection | 2/14/2012 | 2/14/2012 | 2/16/2012 | P | PART |
Forrest France
|
|
|
Completed notification testing and EOL voltage measurements for new nac's at the remodel area. Noted one non-functional strobe at the SRO office, remainder of test passed.
|
INSP-Final Inspection | 2/15/2012 | 2/15/2012 | 2/15/2012 | P | FAIL |
Troy Cobbley
|
|
|
Everything is complete except that to final the project I need the requested alarm report for monday and tuesday. Inspection rescheduled for tomorrow morning per conversation with CM company.
|
INSP-Final Inspection | 2/13/2012 | 2/14/2012 | 2/14/2012 | A | FAIL |
Troy Cobbley
|
|
|
The corrections I had red lined have been addressed and the duct smoke detectors tested. As-builts will be needed showing the correct hvac unit/detector. Need the NAC circuits tested, sprinkler flow switches tested, a print out of the signals tested and final paper work for a final sign off.
|
INSP-Final Inspection | 2/10/2012 | 2/13/2012 | 2/13/2012 | P | FAIL |
Troy Cobbley
|
|
|
Todays inspection covered the new NAC panel and its interconnection with the existing FACP the testing of the new smoke detectors in Corridor 222 and the fire sprinkler riser tamper switches. The location of the inspectors tests were not immediately known. Heights and spacing of all of the new audio/visuals was also performed. I found several locations wheres a/v's were missing, a/v's overspaced and manual pull stations missing. The duct smoke detectors and NAC circuit testing was not performed. I spoke to Chad with Bishop Kelly about signage on the FACP room door and the fire sprinkler riser room door. I spoke to Colton about as-builts showing the door holder being deleted in Corridor 222.
|
INSP-Conference | 2/1/2012 | 2/1/2012 | 2/1/2012 | P | DONE |
Troy Cobbley
|
|
|
I went over duct smoke detector placement with Mountain Power Electric.
|
Plan assigned to (Stephanie) | 11/30/2011 | | 12/7/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 12/7/2011 | | DONE |
|
|
|
|
Alarm Plan Check | 12/7/2011 | | 12/7/2011 | | PASS |
Stephanie L. Cobbley
|
|
|
Approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 12/7/2011 | | DONE |
|
|
|
Approved redlined plans available at front counter.
|
Inspection Record Card- Fire | 12/7/2011 | | 12/7/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 12/7/2011 | | DONE |
|
|
|
t/c w kevin - permit ready and fees given
|
Permit Ready to Issue | | | 12/7/2011 | | DONE |
|
|
|
|
Issue and Print Permit | | | 12/7/2011 | | DONE |
Barbara Stitt
|
|
|
|
Application received | | | 11/30/2011 | | |
|
|
|
|