Permit Information
Permit NumberFIR11-00650
StatusFinaled
Name TRI STATE ELECTRIC
Site Address 1211 S COLE RD
Project NameLDS TEMPLE
Customer Number 
ePlanReviewNo
Description
8/27/12 Plan Modification (no initiating devices affected): This plan modification is to incorporate field modifications and previous plan review redlines and comments. In addition, per the State Elevator Inspector, the two existing elevators are not required to have recall or shunt trip operations so the monitor modules and control modules for those functions have been deleted.
1/12/12: NOTE: A plan modification is required to be submitted and approved prior to calling for a final inspection.
This fire alarm permit is to replace the existing fire alarm system. This permit includes providing sprinkler system monitoring, elevator recall, HVAC monitoring/shutdown, a full manual system, and full notification throughout the building.
Associated building permit: BLD10-02069
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  9/26/2012 DONE
Plans taken to records for scanning.
INSP-Final Inspection9/6/20129/6/20129/6/2012PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection8/31/20129/5/20129/5/2012AFAIL
DetailsTroy Cobbley
NFPA 72 form is not completely filled out.
Telephone call  9/5/2012 DONE
Spoke to Scott with Jacobsen Construction to return his call and also get verification that Rob Ahten with Protex has been authorized by the fire alarm designer/engineer to make design decisions. He stated that he does have on file documentation from the engineer giving Rob Ahten that authorization.
Telephone call  9/5/2012 DONE
Received a phone call from Rob Ahten clarifying the design intent for connections to a damper located in the elevator control room. He stated that the damper is a fire damper on a venting louver for the elvator. He said a smoke detector (will cover the area of the room under the listed spacing) was provided along with a control module to shut the damper upon actuation of the detector. He stated that the smoke detector would not only shut down the damper but also intiate a general alarm condition. He also clarified that the elevator control room smoke detector would be the only device to close the damper. I let him know that, based on his description, the design intent meets IFC and NFPA 72 requirements.
Telephone call  9/5/2012 DONE
Spoke to the inspector to let him know of my phone discussions with Scott (Jacobsen Construction) and Rob (Protex) and that the way the damper is being connected to the fire alarm system per Rob's description does meet code requirements and is acceptable as an as-built condition.
INSP-Final Inspection8/31/20129/4/20129/4/2012AFAIL
DetailsTroy Cobbley
Repair the PIV, provide notification in the basement dressing rooms, provide activation for the fire/smoke damper in the elevator room wall and provide as-builts which include the address changes, additional devices with revised EOL and voltage calculations.
INSP-Final Inspection8/29/20128/31/20128/31/2012ANR
DetailsForrest France
Pending corrections.
INSP-Final Inspection8/29/20128/30/20128/30/2012APART
DetailsForrest France
Completed initial walkthrough of the basement, first floor and mechanical mezzanine areas. Items noted include; missing lock and labels at the panel breakers, need to relocate the SD at the FACP, provide signage at the door to the FACP room, relocate MP at the riser, include added FSD at the elevator machine room on record drawings, provide missing occupant notification at the pantry locker/dressing room and the shop RR, replace ceiling mount horn at the chiller, need to verify min. dB is met at the storage rooms, visual coverage at the mens and womens dressing rooms 010 and 012 may be insufficient, provide strobe at the NW womens locker WC, provide coverage or a separation door at closet 109, instruction room 161 cd settings revised while on site, a/v at the brides room relocated to the opposite wall, "storage" room 196 will need occupant notification due to change in room use, need to verify dB measurements at the mechanical mezzanine and listing for concealed a/v's on the first floor.
INSP-Final Inspection8/29/20128/29/20128/29/2012PCANC
DetailsTroy Cobbley
overbooked
(F) Reprint permit  8/29/2012 DONE
CHANGE STATUS TO (ISS)  8/29/2012  
Telephone call  8/28/2012 DONE
Mr. Barnes returned my phone call and said that he would look in to it and email me.
Miscellaneous action  8/28/2012 DONE
Recieved an email from Mr. Barnes stating that the other elevator is a freight elevator only and as long as it did not have any recall controls then it did not have to have recall or shunt trip functions.
Alarm Plan Check8/28/2012 8/28/2012 PASS
DetailsStephanie L. Cobbley
Plan modification approved with redlines and review comments.
PLANS TAKEN FRONT DESK ALARM  8/28/2012 DONE
Plan modification documents taken to permit technician for processing.
Inspection Record Card- Fire8/28/2012 8/28/2012 DONE
DetailsTisha Gallop
Permit Ready to Issue  8/28/2012 DONE
DetailsTisha Gallop
Telephone call  8/28/2012 DONE
DetailsTisha Gallop
called Daric/Tri-State Ele. and left mssg permit is ready and fee.
Telephone call  8/27/2012 DONE
Left a message for the state elevator inspector regarding an email from him that was forwarded to me. The letter from Mr. Barnes stated the elevator did not require recall or shunt trip functions. I asked for clarification because there are two elevators shown on the plans.
Plan resubmittals received  8/17/2012 DONE
Plan mod - rec'd 2 sets
FIR-Aging Inspection6/13/20126/13/20126/20/2012 NR
DetailsTroy Cobbley
work is in progress
Miscellaneous action  6/4/2012 DONE
Received an email from Protex regarding a field panel modification that had been done. He stated that two power supplies have been taken from their factory 'cans' and placed together in another 'can' and connected together to form one remote power supply. He wanted verification of the ability to use this configuration. I explained that what he described voids the manufacturers UL listing and emailed him the IFC and NFPA 72 sections that explained why this is not allowed. I also recommended he consult with the manufacturer because now the two power supplies that were removed from their factory 'can' may not be listed anymore individually either now that they have been modified; therefore two new power supplies may need to be purchased.
Issue and Print Permit  1/26/2012 DONE
Alarm Plan Check1/12/2012 1/12/2012 PASS
DetailsStephanie L. Cobbley
Plans approved with redlines and review comments - and with the understanding that a plan modification is required to be submitted and approved prior to calling for a final inspection.
PLANS TAKEN FRONT DESK ALARM  1/12/2012 DONE
Approved redlined plans available at front counter.
Inspection Record Card- Fire1/12/2012 1/12/2012 DONE
DetailsPatricia Smith
Telephone call  1/12/2012 DONE
left vm for jay - permit ready and fees given
Permit Ready to Issue  1/12/2012 DONE
Details
Plan assigned to (Stephanie)12/6/2011 1/12/2012 DONE
DetailsStephanie L. Cobbley
Plan resubmittals received  1/3/2012 DONE
DetailsTisha Gallop
received application and two copies of submittal folder and plans.
Miscellaneous action  12/16/2011 DONE
DetailsTisha Gallop
picked up denied plans
1st review completed  12/15/2011 DONE
Alarm Plan Check12/15/2011 12/15/2011 FAIL
DetailsStephanie L. Cobbley
Plans denied - see review comments and redlined plans
Miscellaneous action  12/15/2011 DONE
Faxed copy of review comments to contractor indicating a resubmittal is required.
Miscellaneous action  12/15/2011 DONE
E-mailed the review comments to the fire alarm vendor at his previous request for his information.
Miscellaneous action  12/15/2011 DONE
Denied plans available at front counter for contractor to pick up.
Application received  12/6/2011 DONE
DetailsBarbara Stitt
Case Summary  12/6/2011 DONE
DetailsBarbara Stitt