Miscellaneous action | | | 9/26/2012 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 9/6/2012 | 9/6/2012 | 9/6/2012 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 8/31/2012 | 9/5/2012 | 9/5/2012 | A | FAIL |
Troy Cobbley
|
|
|
NFPA 72 form is not completely filled out.
|
Telephone call | | | 9/5/2012 | | DONE |
|
|
|
Spoke to Scott with Jacobsen Construction to return his call and also get verification that Rob Ahten with Protex has been authorized by the fire alarm designer/engineer to make design decisions. He stated that he does have on file documentation from the engineer giving Rob Ahten that authorization.
|
Telephone call | | | 9/5/2012 | | DONE |
|
|
|
Received a phone call from Rob Ahten clarifying the design intent for connections to a damper located in the elevator control room. He stated that the damper is a fire damper on a venting louver for the elvator. He said a smoke detector (will cover the area of the room under the listed spacing) was provided along with a control module to shut the damper upon actuation of the detector. He stated that the smoke detector would not only shut down the damper but also intiate a general alarm condition. He also clarified that the elevator control room smoke detector would be the only device to close the damper. I let him know that, based on his description, the design intent meets IFC and NFPA 72 requirements.
|
Telephone call | | | 9/5/2012 | | DONE |
|
|
|
Spoke to the inspector to let him know of my phone discussions with Scott (Jacobsen Construction) and Rob (Protex) and that the way the damper is being connected to the fire alarm system per Rob's description does meet code requirements and is acceptable as an as-built condition.
|
INSP-Final Inspection | 8/31/2012 | 9/4/2012 | 9/4/2012 | A | FAIL |
Troy Cobbley
|
|
|
Repair the PIV, provide notification in the basement dressing rooms, provide activation for the fire/smoke damper in the elevator room wall and provide as-builts which include the address changes, additional devices with revised EOL and voltage calculations.
|
INSP-Final Inspection | 8/29/2012 | 8/31/2012 | 8/31/2012 | A | NR |
Forrest France
|
|
|
Pending corrections.
|
INSP-Final Inspection | 8/29/2012 | 8/30/2012 | 8/30/2012 | A | PART |
Forrest France
|
|
|
Completed initial walkthrough of the basement, first floor and mechanical mezzanine areas. Items noted include; missing lock and labels at the panel breakers, need to relocate the SD at the FACP, provide signage at the door to the FACP room, relocate MP at the riser, include added FSD at the elevator machine room on record drawings, provide missing occupant notification at the pantry locker/dressing room and the shop RR, replace ceiling mount horn at the chiller, need to verify min. dB is met at the storage rooms, visual coverage at the mens and womens dressing rooms 010 and 012 may be insufficient, provide strobe at the NW womens locker WC, provide coverage or a separation door at closet 109, instruction room 161 cd settings revised while on site, a/v at the brides room relocated to the opposite wall, "storage" room 196 will need occupant notification due to change in room use, need to verify dB measurements at the mechanical mezzanine and listing for concealed a/v's on the first floor.
|
INSP-Final Inspection | 8/29/2012 | 8/29/2012 | 8/29/2012 | P | CANC |
Troy Cobbley
|
|
|
overbooked
|
(F) Reprint permit | | | 8/29/2012 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 8/29/2012 | | |
|
|
|
|
Telephone call | | | 8/28/2012 | | DONE |
|
|
|
Mr. Barnes returned my phone call and said that he would look in to it and email me.
|
Miscellaneous action | | | 8/28/2012 | | DONE |
|
|
|
Recieved an email from Mr. Barnes stating that the other elevator is a freight elevator only and as long as it did not have any recall controls then it did not have to have recall or shunt trip functions.
|
Alarm Plan Check | 8/28/2012 | | 8/28/2012 | | PASS |
Stephanie L. Cobbley
|
|
|
Plan modification approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 8/28/2012 | | DONE |
|
|
|
Plan modification documents taken to permit technician for processing.
|
Inspection Record Card- Fire | 8/28/2012 | | 8/28/2012 | | DONE |
Tisha Gallop
|
|
|
|
Permit Ready to Issue | | | 8/28/2012 | | DONE |
Tisha Gallop
|
|
|
|
Telephone call | | | 8/28/2012 | | DONE |
Tisha Gallop
|
|
|
called Daric/Tri-State Ele. and left mssg permit is ready and fee.
|
Telephone call | | | 8/27/2012 | | DONE |
|
|
|
Left a message for the state elevator inspector regarding an email from him that was forwarded to me. The letter from Mr. Barnes stated the elevator did not require recall or shunt trip functions. I asked for clarification because there are two elevators shown on the plans.
|
Plan resubmittals received | | | 8/17/2012 | | DONE |
|
|
|
Plan mod - rec'd 2 sets
|
FIR-Aging Inspection | 6/13/2012 | 6/13/2012 | 6/20/2012 | | NR |
Troy Cobbley
|
|
|
work is in progress
|
Miscellaneous action | | | 6/4/2012 | | DONE |
|
|
|
Received an email from Protex regarding a field panel modification that had been done. He stated that two power supplies have been taken from their factory 'cans' and placed together in another 'can' and connected together to form one remote power supply. He wanted verification of the ability to use this configuration. I explained that what he described voids the manufacturers UL listing and emailed him the IFC and NFPA 72 sections that explained why this is not allowed. I also recommended he consult with the manufacturer because now the two power supplies that were removed from their factory 'can' may not be listed anymore individually either now that they have been modified; therefore two new power supplies may need to be purchased.
|
Issue and Print Permit | | | 1/26/2012 | | DONE |
|
|
|
|
Alarm Plan Check | 1/12/2012 | | 1/12/2012 | | PASS |
Stephanie L. Cobbley
|
|
|
Plans approved with redlines and review comments - and with the understanding that a plan modification is required to be submitted and approved prior to calling for a final inspection.
|
PLANS TAKEN FRONT DESK ALARM | | | 1/12/2012 | | DONE |
|
|
|
Approved redlined plans available at front counter.
|
Inspection Record Card- Fire | 1/12/2012 | | 1/12/2012 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 1/12/2012 | | DONE |
|
|
|
left vm for jay - permit ready and fees given
|
Permit Ready to Issue | | | 1/12/2012 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 12/6/2011 | | 1/12/2012 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Plan resubmittals received | | | 1/3/2012 | | DONE |
Tisha Gallop
|
|
|
received application and two copies of submittal folder and plans.
|
Miscellaneous action | | | 12/16/2011 | | DONE |
Tisha Gallop
|
|
|
picked up denied plans
|
1st review completed | | | 12/15/2011 | | DONE |
|
|
|
|
Alarm Plan Check | 12/15/2011 | | 12/15/2011 | | FAIL |
Stephanie L. Cobbley
|
|
|
Plans denied - see review comments and redlined plans
|
Miscellaneous action | | | 12/15/2011 | | DONE |
|
|
|
Faxed copy of review comments to contractor indicating a resubmittal is required.
|
Miscellaneous action | | | 12/15/2011 | | DONE |
|
|
|
E-mailed the review comments to the fire alarm vendor at his previous request for his information.
|
Miscellaneous action | | | 12/15/2011 | | DONE |
|
|
|
Denied plans available at front counter for contractor to pick up.
|
Application received | | | 12/6/2011 | | DONE |
Barbara Stitt
|
|
|
|
Case Summary | | | 12/6/2011 | | DONE |
Barbara Stitt
|
|
|
|