Miscellaneous action | | | 1/20/2012 | | DONE |
|
|
|
Plans taken to records for scanning.
|
Plan resubmittals received | | | 1/6/2012 | | DONE |
Tisha Gallop
|
|
|
received by mail one set of as-builts; taken to Steph.
|
INSP-Final Inspection | 12/20/2011 | 12/21/2011 | 12/21/2011 | A | PASS |
Troy Cobbley
|
|
|
permit finaled
|
Miscellaneous action | | | 12/21/2011 | | DONE |
|
|
|
Accepted a pdf in an email for 'intent' of as-builts due to the engineer's CAD person being out of the office. The engineer will have hard copies of a CAD version to me this week. I also let the inspector know the fire alarm permit can proceed the same as if the as-builts were provided.
|
INSP-Final Inspection | 12/20/2011 | 12/20/2011 | 12/20/2011 | P | FAIL |
Troy Cobbley
|
|
|
The new horn/strobes that have been installed are not the devices that have been submitted. Also as-built plans were not provided as required due to the NAC errors. Provide a data sheet for the new devices to plan review and as-builts.
|
Plan assigned to (Stephanie) | 12/13/2011 | | 12/16/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 12/16/2011 | | DONE |
|
|
|
|
Alarm Plan Check | 12/16/2011 | | 12/16/2011 | | PASS |
Stephanie L. Cobbley
|
|
|
Plans approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 12/16/2011 | | DONE |
|
|
|
Approved redlined plans available at front counter.
|
Inspection Record Card- Fire | 12/16/2011 | | 12/16/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 12/16/2011 | | DONE |
|
|
|
left vm for tim - permit ready and fees given
|
Permit Ready to Issue | | | 12/16/2011 | | DONE |
|
|
|
|
Issue and Print Permit | | | 12/16/2011 | | DONE |
|
|
|
|
Application received | | | 12/13/2011 | | |
|
|
|
|