Miscellaneous action | | | 4/12/2012 | | DONE |
|
|
|
Plans taken to records for scanning
|
INSP-Final Inspection | 4/6/2012 | 4/9/2012 | 4/9/2012 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Final Inspection | 3/20/2012 | 3/23/2012 | 3/23/2012 | A | FAIL |
Troy Cobbley
|
|
|
The zones being reported to the fire alarm panel annunciator do not match those listed on the approved plans. As-built plans are required that match. The zone for the wet system water flow switch reported incorrectly as a smoke detector. This also will need to be changed. The four new duct smoke detectors, as shown on the approved plans, do not shut down the hvac units as required. They will need to be corrected and re-tested.
|
Issue and Print Permit | | | 1/13/2012 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 12/15/2011 | | 12/23/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 12/23/2011 | | DONE |
|
|
|
|
Alarm Plan Check | 12/23/2011 | | 12/23/2011 | | PASS |
Stephanie L. Cobbley
|
|
|
Plans approved with review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 12/23/2011 | | DONE |
|
|
|
Approved plans available at front counter.
|
Inspection Record Card- Fire | 12/23/2011 | | 12/23/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 12/23/2011 | | DONE |
|
|
|
left vm for dave - permit ready and fees given
|
Permit Ready to Issue | | | 12/23/2011 | | DONE |
|
|
|
|
Case Summary | | | 12/15/2011 | | DONE |
|
|
|
|
Application received | | | 12/15/2011 | | |
|
|
|
|