Permit Information
Permit NumberFIR11-00668
StatusFinaled
Name ADT SECURITY SERVICES INC
Site Address 1116 N COLE RD
Project NameBoise Racquet and Swim Club
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to connect existing tamper switches and a low air switch to the existing fire alarm panel (previously not done for unknown reasons), install a new manual pull station at the riser, connect 4 new duct detectors with remote indicators, and install a new smoke detector above the FACP.

Associated building permit: BLD11-02634 **(BOISE RACQUET AND SWIM CLUB – Club House)** Application for inspection to determine requirements for issuance of a Certificate of Occupancy for an existing 12,000 square foot club house building. NO NEW WORK IS AUTHORIZED UNDER THIS PERMIT. This tenant space has always been occupied by Boise Racquet and Swim Club. Over the years remodels and additions have been done, but a new C of O addressing the entire building has never been issued. There are no changes to occupancy or use under this permit. TLW
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  4/12/2012 DONE
Plans taken to records for scanning
INSP-Final Inspection4/6/20124/9/20124/9/2012PPASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection3/20/20123/23/20123/23/2012AFAIL
DetailsTroy Cobbley
The zones being reported to the fire alarm panel annunciator do not match those listed on the approved plans. As-built plans are required that match. The zone for the wet system water flow switch reported incorrectly as a smoke detector. This also will need to be changed. The four new duct smoke detectors, as shown on the approved plans, do not shut down the hvac units as required. They will need to be corrected and re-tested.
Issue and Print Permit  1/13/2012 DONE
Plan assigned to (Stephanie)12/15/2011 12/23/2011 DONE
DetailsStephanie L. Cobbley
1st review completed  12/23/2011 DONE
Alarm Plan Check12/23/2011 12/23/2011 PASS
DetailsStephanie L. Cobbley
Plans approved with review comments.
PLANS TAKEN FRONT DESK ALARM  12/23/2011 DONE
Approved plans available at front counter.
Inspection Record Card- Fire12/23/2011 12/23/2011 DONE
DetailsPatricia Smith
Telephone call  12/23/2011 DONE
left vm for dave - permit ready and fees given
Permit Ready to Issue  12/23/2011 DONE
Details
Case Summary  12/15/2011 DONE
Application received  12/15/2011