Permit Information
Permit NumberFIR11-00679
StatusFinaled
Name CRANE ALARM COMPANY
Site Address 7031 S EISENMAN RD
Project NamePOWERBAR-HAND SIFTING ROOM
Customer Number 
ePlanReviewNo
Description
This quick permit is to relocate and reduce the candela rating of an existing horn/strobe and add a new horn/strobe due to an existing room being divided into two for a tenant remodel. Approval is subject to field measurement of the EOL voltage drop. For appliances with an operating voltage range of 16V – 33V, the minimum acceptable voltage is 19.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V. UL 864, Standard for Control Units for Fire Signaling Systems.The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector. There are no written review comments. Associated building permit: BLD11-02851 POWERBAR-HAND SIFTING ROOM- Permit for minor tenant improvements to construct approximately 14 lineal feet of interior nonbearing partition wall separating sifting line one from sifting line two per the approved plans. "This building is fully Fire Sprinklered with an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. CDM
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  1/20/2012 DONE
Plans taken to records for scanning.
INSP-Final Inspection1/3/20121/4/20121/4/2012APASS
DetailsForrest France
Scope of fire alarm work passed functional testing. Permit finaled.
Issue and Print Permit  12/27/2011 DONE
DetailsBarbara Stitt
Plan assigned to (Stephanie)12/21/2011 12/22/2011 DONE
DetailsStephanie L. Cobbley
Plan assigned to (Stephanie)12/21/2011 12/22/2011 DONE
DetailsStephanie L. Cobbley
1st review completed  12/22/2011 DONE
Alarm Plan Check12/22/2011 12/22/2011 PASS
DetailsStephanie L. Cobbley
Quick permit approved - no written review comments.
PLANS TAKEN FRONT DESK ALARM  12/22/2011 DONE
Approved quick permit plans available at front counter.
Inspection Record Card- Fire12/22/2011 12/22/2011 DONE
DetailsPatricia Smith
Telephone call  12/22/2011 DONE
t/c w jessica - permit ready and fees given
Permit Ready to Issue  12/22/2011 DONE
Details
Application received  12/21/2011