Permit Information
Permit NumberFIR11-00683
StatusFinaled
Name ENTERPRISE ELECTRIC
Site Address 11311 W CHINDEN BLVD
Project NameHP BLDG 7-PACKAGE TEST LAB EXP
Customer Number 
ePlanReviewNo
Description
This quick permit is to provide two new horn/strobes to the existing fire alarm system to accomodate a tenant remodel. Approval is subject to field measurement of the EOL voltage drop. For appliances with an operating voltage range of 16V – 33V, the minimum acceptable voltage is 19.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V. UL 864, Standard for Control Units for Fire Signaling Systems. The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector. There are no written review comments. Associated building permit: BLD11-02973 (HP BLDG 7 - PACKAGE TEST LAB EXPANSION) Construct interior non-bearing non-rated walls to create a Package Test Lab in conjunction with recent test lab relocation and testing facilities. This new room will occupy a portion of the existing Shipping Receiving Area; relocated double doors installed; modified ceiling; mechanical & electrical services upgrades for new use. A separate permit is required before any work can be done for any modifications of the existing sprinkler or alarm systems as regulated by the Fire Department. Limited rack storage of products used in packaging test lab, with storage height limited to 12 feet or less. Racks to be secured to each other, the floor and / or walls to provide lateral support. Scope of work will not increase building area, occupant load or occupancy use groups. drs
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  4/12/2012 DONE
Plans taken to records for scanning
INSP-Final Inspection3/29/20123/29/20123/29/2012PPASS
DetailsTroy Cobbley
Permit finaled. EOL voltages verified.
INSP-Alarm Testing3/28/20123/29/20123/29/2012APASS
DetailsTroy Cobbley
Testing complete
Meeting  3/2/2012 DONE
Per the Fire Code Official; the irregular voltage readings identified on the secondary energy source shall not prohibit this alarm inspection from being approved for occupancy. *SJA*
INSP-Alarm Testing2/3/20122/6/20122/3/2012ACANC
DetailsTroy Cobbley
Phone #: ###-#### >> Inspection requested via web by Clint Tate Inspection cancelled from web by: Clint Tate
INSP-Alarm Testing2/2/20122/3/20122/2/2012ACANC
DetailsTroy Cobbley
Jason (wants special at 5:15am, he will call you on 2/2 pm to see if possible) Phone #: ###-####
INSP-Alarm Testing1/20/20121/23/20121/23/2012AFAIL
DetailsTroy Cobbley
A minimum reading of 19.6 volts could not be verified with the volt meter
Issue and Print Permit  1/5/2012 DONE
Permit Ready to Issue  1/4/2012 DONE
Application received  12/23/2011  
Plan assigned to (Stephanie)12/23/2011 12/23/2011 DONE
DetailsStephanie L. Cobbley
Plan assigned to (Stephanie)12/23/2011 12/23/2011 DONE
DetailsStephanie L. Cobbley
1st review completed  12/23/2011 DONE
Alarm Plan Check12/23/2011 12/23/2011 PASS
DetailsStephanie L. Cobbley
Quick permit plans approved - no written review comments.
PLANS TAKEN FRONT DESK ALARM  12/23/2011 DONE
Approved quick permit plans available at front counter.
Telephone call  12/23/2011 DONE
t/c w jeremy at enterprise - permit ready and fees given
Inspection Record Card- Fire12/23/2011 12/23/2011 DONE
DetailsPatricia Smith