Miscellaneous action | | | 4/12/2012 | | DONE |
|
|
|
Plans taken to records for scanning
|
INSP-Final Inspection | 3/29/2012 | 3/29/2012 | 3/29/2012 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled. EOL voltages verified.
|
INSP-Alarm Testing | 3/28/2012 | 3/29/2012 | 3/29/2012 | A | PASS |
Troy Cobbley
|
|
|
Testing complete
|
Meeting | | | 3/2/2012 | | DONE |
|
|
|
Per the Fire Code Official; the irregular voltage readings identified on the secondary energy source shall not prohibit this alarm inspection from being approved for occupancy. *SJA*
|
INSP-Alarm Testing | 2/3/2012 | 2/6/2012 | 2/3/2012 | A | CANC |
Troy Cobbley
|
|
|
Phone #: ###-#### >> Inspection requested via web by Clint Tate Inspection cancelled from web by: Clint Tate
|
INSP-Sprinkler Rough-in/Hydro | 2/3/2012 | 2/6/2012 | 2/3/2012 | A | CANC |
Troy Cobbley
|
|
|
Phone #: ###-#### >> Inspection requested via web by Clint Tate Inspection cancelled from web by: Clint Tate
|
Issue permit | | | 2/1/2012 | | DONE |
|
|
|
Payment received via Govolutions
|
INSP-Alarm Testing | 1/20/2012 | 1/23/2012 | 1/23/2012 | A | FAIL |
Troy Cobbley
|
|
|
A minimum reading of 19.6 volts could not be verified with the volt meter and it appears that there are more than three strobe rates.
|
INSP-Sprinkler Rough-in/Hydro | 1/20/2012 | 1/23/2012 | 1/20/2012 | A | CANC |
Troy Cobbley
|
|
|
Phone #: ###-#### >> Inspection requested via web by Clint Tate Inspection cancelled from web by: Clint Tate
|
INSP-Sprinkler Rough-in/Hydro | 1/19/2012 | 1/20/2012 | 1/20/2012 | A | DONE |
Troy Cobbley
|
|
|
This was a pre-inspection. I found strobe coverage overspaced off of the breakroom wall. I discussed the need for EOL voltage verification.
|
Plan assigned to (Stephanie) | 12/27/2011 | | 12/29/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 12/29/2011 | | DONE |
|
|
|
|
Alarm Plan Check | 12/29/2011 | | 12/29/2011 | | PASS |
Stephanie L. Cobbley
|
|
|
Plans approved with review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 12/29/2011 | | DONE |
|
|
|
Approved plans available at front counter.
|
Inspection Record Card- Fire | 12/29/2011 | | 12/29/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 12/29/2011 | | DONE |
|
|
|
t/c w jeremy - permit ready and fees given
|
Permit Ready to Issue | | | 12/29/2011 | | DONE |
|
|
|
|
Issue and Print Permit | | | 12/29/2011 | | DONE |
Barbara Stitt
|
|
|
|
Application received | | | 12/27/2011 | | DONE |
Barbara Stitt
|
|
|
|