Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberFIR11-00688
StatusFinaled
Name ENTERPRISE ELECTRIC
Site Address 11311 W CHINDEN BLVD
Project NameHP BLDG 7 LOWER CTSL LAB
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to provide a new NAC panel and new notification devices to accommodate a tenant remodel involving the addition of rows of high server racks. The new NAC panel is to be located on the mezzanine. There is no associated building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  4/12/2012 DONE
Plans taken to records for scanning
INSP-Final Inspection3/29/20123/29/20123/29/2012PPASS
DetailsTroy Cobbley
Permit finaled. EOL voltages verified.
INSP-Alarm Testing3/28/20123/29/20123/29/2012APASS
DetailsTroy Cobbley
Testing complete
Meeting  3/2/2012 DONE
Per the Fire Code Official; the irregular voltage readings identified on the secondary energy source shall not prohibit this alarm inspection from being approved for occupancy. *SJA*
INSP-Alarm Testing2/3/20122/6/20122/3/2012ACANC
DetailsTroy Cobbley
Phone #: ###-#### >> Inspection requested via web by Clint Tate Inspection cancelled from web by: Clint Tate
INSP-Sprinkler Rough-in/Hydro2/3/20122/6/20122/3/2012ACANC
DetailsTroy Cobbley
Phone #: ###-#### >> Inspection requested via web by Clint Tate Inspection cancelled from web by: Clint Tate
Issue permit  2/1/2012 DONE
Payment received via Govolutions
INSP-Alarm Testing1/20/20121/23/20121/23/2012AFAIL
DetailsTroy Cobbley
A minimum reading of 19.6 volts could not be verified with the volt meter and it appears that there are more than three strobe rates.
INSP-Sprinkler Rough-in/Hydro1/20/20121/23/20121/20/2012ACANC
DetailsTroy Cobbley
Phone #: ###-#### >> Inspection requested via web by Clint Tate Inspection cancelled from web by: Clint Tate
INSP-Sprinkler Rough-in/Hydro1/19/20121/20/20121/20/2012ADONE
DetailsTroy Cobbley
This was a pre-inspection. I found strobe coverage overspaced off of the breakroom wall. I discussed the need for EOL voltage verification.
Plan assigned to (Stephanie)12/27/2011 12/29/2011 DONE
DetailsStephanie L. Cobbley
1st review completed  12/29/2011 DONE
Alarm Plan Check12/29/2011 12/29/2011 PASS
DetailsStephanie L. Cobbley
Plans approved with review comments.
PLANS TAKEN FRONT DESK ALARM  12/29/2011 DONE
Approved plans available at front counter.
Inspection Record Card- Fire12/29/2011 12/29/2011 DONE
DetailsPatricia Smith
Telephone call  12/29/2011 DONE
t/c w jeremy - permit ready and fees given
Permit Ready to Issue  12/29/2011 DONE
Details
Issue and Print Permit  12/29/2011 DONE
DetailsBarbara Stitt
Application received  12/27/2011 DONE
DetailsBarbara Stitt