Miscellaneous action | | | 7/12/2012 | | PASS |
|
|
|
Sent to records for scanning.
|
INSP-Final Inspection | 5/4/2012 | 5/4/2012 | 5/4/2012 | P | PASS |
Forrest France
|
|
|
UG flush, flow switch test and final walkthrough passed. Permit finaled.
|
INSP-Sprinkler Rough-in/Hydro | 2/28/2012 | 2/29/2012 | 2/29/2012 | P | PASS |
Tim Frost
|
|
|
Rough in was ok. Plastic, was spread over the piping but there was no insulation. One bathroom had changed. There will be a pocket door that separates the area. In essecence, the are will become to small bathrooms which do not require sprinklers.
|
INSP-Supply line flush | 1/26/2012 | 1/26/2012 | 1/26/2012 | P | PART |
Troy Cobbley
|
|
|
Rough to cover the underground passed. Underground flush was not performed.
|
INSP-Supply line flush | 1/19/2012 | 1/20/2012 | 1/20/2012 | P | FAIL |
Troy Cobbley
|
|
|
The underground supply line is not buried deep enough, has been installed as 1 1/2" without the 2" starter and is not a continous run to the riser as shown on the plans.
|
Plan assigned to (Tim) | 1/13/2012 | | 1/17/2012 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 1/17/2012 | | 1/17/2012 | | FAIL |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
Miscellaneous action | | | 1/17/2012 | | DONE |
Tim Frost
|
|
|
Emailed review to contractor
|
Telephone call | | | 1/17/2012 | | DONE |
|
|
|
t/c w sam - permit denied - needs to be picked up and resubmitted
|
Plan resubmittals received | | | 1/17/2012 | | |
|
|
|
|
Sprinkler Plan Check | 1/17/2012 | | 1/17/2012 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 1/17/2012 | | FAIL |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/17/2012 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 1/17/2012 | | 1/17/2012 | | DONE |
Patricia Smith
|
|
|
|
Inspection Record Card- Fire | 1/17/2012 | | 1/17/2012 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 1/17/2012 | | DONE |
|
|
|
t/c w sam - permit ready and fees given
|
Permit Ready to Issue | | | 1/17/2012 | | DONE |
|
|
|
|
Issue and Print Permit | | | 1/17/2012 | | DONE |
Barbara Stitt
|
|
|
|
Application received | | | 1/13/2012 | | |
|
|
|
|