Miscellaneous action | | | 11/30/2012 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 10/16/2012 | 10/17/2012 | 10/17/2012 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
FIR-Aging Inspection | 9/26/2012 | 9/26/2012 | 9/26/2012 | | NR |
Troy Cobbley
|
|
|
Per general contractor the work to fix the sync'ing problem is still being worked on.
|
INSP-Final Inspection | 6/27/2012 | 6/28/2012 | 6/28/2012 | A | FAIL |
Troy Cobbley
|
|
|
Per the acting fire marshal, Gordon Goldsmith, the horns and the strobes need to meet NFPA 72 requirements for syncronization prior to a final sign off for the fire alarm permits.
|
Meeting | | | 6/28/2012 | | DONE |
|
|
|
Onsite meeting with the PDS/Fire inspector, Fire Marshal (Captain Goldsmith), and General Contractor. A second fire alarm system test was conducted to evaluate audible synchronization between existing horns and new devices installed. It was determined by the Fire Marshal that the audible synchronization was not acceptable and would need to be corrected and comply with temporal pattern.
|
INSP-Final Inspection | 6/27/2012 | 6/27/2012 | 6/27/2012 | P | FAIL |
Troy Cobbley
|
|
|
The strobes sync. but the horns do not. Per the contractor they did sync until the two additional devices were added today. The fire alarm contractor is going to investigate the cause and/or contact the fire marshal if this is a new device versus an old device issue. EOL was verified.
|
CHANGE STATUS TO (ISS) | | | 6/27/2012 | | DONE |
Barbara Stitt
|
|
|
|
(F) Reprint permit | | | 6/27/2012 | | DONE |
Barbara Stitt
|
|
|
|
Plan resubmittals received | | | 6/26/2012 | | DONE |
Tisha Gallop
|
|
|
received application and two sets of submittal folder and plans; routed to Fire
|
Inspection Record Card- Fire | 6/26/2012 | | 6/26/2012 | | DONE |
Darla L Downs
|
|
|
|
Permit Ready to Issue | | | 6/26/2012 | | |
|
|
|
|
Telephone call | | | 6/26/2012 | | |
|
|
|
6-26-12 called Daric- Tri State Electric permit ready ///dld
|
Alarm Plan Check | 6/25/2012 | | 6/25/2012 | | FAIL |
Stephanie L. Cobbley
|
|
|
Plans denied - see redlines and review comments.
|
Miscellaneous action | | | 6/25/2012 | | DONE |
|
|
|
Fire ALarm contractor emailed letting them know the plans are being denied and that they can pick up the redlined plans and review comments from the permit counter.
|
Miscellaneous action | | | 6/25/2012 | | DONE |
|
|
|
Denied plans taken to front counter.
|
Plan assigned to (Stephanie) | 3/20/2012 | | 6/21/2012 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Plan resubmittals received | | | 6/18/2012 | | DONE |
|
|
|
rec'd two sets
|
Alarm Plan Check | 4/2/2012 | | 4/2/2012 | | FAIL |
Stephanie L. Cobbley
|
|
|
Plans denied - the submitted fire alarm plans do not match/encompass the building permit scope of work. Please see review comments and redlined plans.
|
Miscellaneous action | | | 4/2/2012 | | DONE |
|
|
|
Faxed review comments to Applicant
|
Miscellaneous action | | | 4/2/2012 | | DONE |
|
|
|
emailed Protex (per their request) letting them know the plans are being denied.
|
Plan resubmittals received | | | 3/20/2012 | | DONE |
Tisha Gallop
|
|
|
Plan Modification: Received application, and two copies of submittal documents and plans; routed to SLC
|
INSP-Final Inspection | 2/28/2012 | 2/28/2012 | 2/28/2012 | P | FAIL |
Forrest France
|
|
|
Plans do not match installation, number of devices or scope of work completed.
|
Issue and Print Permit | | | 2/6/2012 | | DONE |
|
|
|
|
(F) Reprint permit | | | 2/6/2012 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 1/24/2012 | | 1/26/2012 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Plan assigned to (Stephanie) | 1/24/2012 | | 1/26/2012 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 1/26/2012 | | DONE |
|
|
|
|
Alarm Plan Check | 1/26/2012 | | 1/26/2012 | | PASS |
Stephanie L. Cobbley
|
|
|
Quick permit approved with redlines - no written review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 1/26/2012 | | DONE |
|
|
|
Approved redlined quick permit plans available at front counter.
|
Inspection Record Card- Fire | 1/26/2012 | | 1/26/2012 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 1/26/2012 | | DONE |
|
|
|
ledt vm for daric - permit ready and fees given
|
Permit Ready to Issue | | | 1/26/2012 | | DONE |
|
|
|
|
Application received | | | 1/24/2012 | | |
|
|
|
|