Miscellaneous action | | | 7/12/2012 | | DONE |
Tim Frost
|
|
|
Sent to Records for scanning.
|
INSP-Final Inspection | 4/24/2012 | 4/24/2012 | 4/26/2012 | P | PASS |
Forrest France
|
|
|
Fire sprinkler permit finaled.
|
INSP-Sprinkler Rough-in/Hydro | 4/23/2012 | 4/24/2012 | 4/24/2012 | A | PART |
Forrest France
|
|
|
Completed satisfactory 24 hr. pneumatic test of the new dry system.
|
INSP-Final Inspection | 4/20/2012 | 4/23/2012 | 4/23/2012 | A | PART |
Forrest France
|
|
|
Begin 24 hr. test of the new dry system at 10:30 AM @41.5psig.
|
INSP-Final Inspection | 4/17/2012 | 4/17/2012 | 4/19/2012 | P | PART |
Forrest France
|
|
|
Final pending 24 hr. test per NFPA 13 2010 24.2.2.1, need to seal or lock the trim valve to the waterflow pressure switch per IFC sec. 903.4 (7).
|
INSP-Sprinkler Rough-in/Hydro | 3/13/2012 | 3/14/2012 | 3/16/2012 | A | PART |
Forrest France
|
|
|
Overhead hydrostatic test at the new dry system completed acceptable. Also discussed seismic bracing and project schedule.
|
Sprinkler Plan Check | 2/8/2012 | | 2/8/2012 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 2/8/2012 | | PASS |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/8/2012 | | DONE |
Tim Frost
|
|
|
|
Permit Ready to Issue | | | 2/8/2012 | | DONE |
Barbara Stitt
|
|
|
|
Inspection Record Card- Fire | 2/8/2012 | | 2/8/2012 | | DONE |
Barbara Stitt
|
|
|
|
Telephone call | | | 2/8/2012 | | DONE |
Barbara Stitt
|
|
|
Emailed Paul and told him that permit is ready & fees due on 2-8-12 @ 9:55am//BAS
|
Issue and Print Permit | | | 2/8/2012 | | DONE |
Barbara Stitt
|
|
|
|
Plan resubmittals received | | | 2/6/2012 | | DONE |
Christina Prado
|
|
|
Received three sets of plans marked FP1 & FP. Also received three sets of plan applications, checklists and calcs
|
Plan assigned to (Scott) | | | 1/30/2012 | | DONE |
Bill Alexander
|
|
|
This permit was created on the web by Paul Marcolina
|
Application received | | | 1/30/2012 | | DONE |
|
|
|
This permit was created on the web by Paul Marcolina
|