INSP-Final Inspection | 4/17/2012 | 4/17/2012 | 4/19/2012 | P | PASS |
Forrest France
|
|
|
Scope of work passed field testing.
|
Alarm Plan Check | 4/10/2012 | | 4/10/2012 | | PASS |
Stephanie L. Cobbley
|
|
|
Plans approved with redlines per site review done 4/5/12 by S. Cobbley
|
PLANS TAKEN FRONT DESK ALARM | | | 4/10/2012 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 4/10/2012 | | DONE |
|
|
|
|
Issue and Print Permit | | | 4/10/2012 | | DONE |
|
|
|
|
1st review completed | | | 3/7/2012 | | FAIL |
|
|
|
|
Alarm Plan Check | 3/7/2012 | | 3/7/2012 | | FAIL |
Stephanie L. Cobbley
|
|
|
Plans failed. The plans indicate in the event of water flow in the dry system, the building notification is not activated. Per IFC, 907.6 Occupant notification systems:"A fire alarm system shall annunciate at the panel and shall initiate occupant notification upon activation, in accordance with Sections 907.6.1 through 907.6.2.3.4. Where a fire alarm system is required by another section of this code, it shall be activated by:
1.Automatic fire detectors.
2.Sprinkler waterflow devices.
3.Manual fire alarm boxes.
4.Automatic fire-extinguishing systems.
|
Application received | | | 2/1/2012 | | DONE |
Stephanie L. Cobbley
|
|
|
This permit was created on the web by Paul Marcolina
|
Application received | | | 2/1/2012 | | DONE |
|
|
|
This permit was created on the web by Paul Marcolina
|