Miscellaneous action | | | 4/24/2012 | | DONE |
Tim Frost
|
|
|
Sent to Records for scanning.
|
INSP-Final Inspection | 3/30/2012 | 3/30/2012 | 3/30/2012 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled.
|
INSP-Sprinkler Rough-in/Hydro | 3/29/2012 | 3/30/2012 | 3/30/2012 | A | PASS |
Troy Cobbley
|
|
|
Hydro test passed for the Ulta Beauty space/system.
|
INSP-Sprinkler Rough-in | 3/28/2012 | 3/29/2012 | 3/29/2012 | A | PART |
Troy Cobbley
|
|
|
Todays inspection was for the ULTA BEAUTY space. Everything appears ok except that the 3" and single 4" branchlines have 1 1/2" pieces in them located at the far main. I requested that TVFP get with plan review to verify that the hydraulic calculations are not adversely effected by this pipe size reduction. Also non-functional rack piping and sprinklers are still hanging from the structure.
|
Issue and Print Permit | | | 3/9/2012 | | DONE |
Tisha Gallop
|
|
|
|
Sprinkler Plan Check | 3/8/2012 | | 3/8/2012 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/8/2012 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 3/8/2012 | | 3/8/2012 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 3/8/2012 | | DONE |
|
|
|
t/c w brodie - permit ready and fees given
|
Permit Ready to Issue | | | 3/8/2012 | | DONE |
|
|
|
|
Plan assigned to (Tim) | 3/1/2012 | | 3/8/2012 | | DONE |
Tim Frost
|
|
|
|
Plan resubmittals received | | | 3/7/2012 | | |
|
|
|
|
Case Summary | | | 3/7/2012 | | DONE |
Barbara Stitt
|
|
|
|
Sprinkler Plan Check | 3/6/2012 | | 3/6/2012 | | FAIL |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 3/6/2012 | | FAIL |
Tim Frost
|
|
|
|
Miscellaneous action | | | 3/6/2012 | | DONE |
Tim Frost
|
|
|
Emailed review to contractor
|
Telephone call | | | 3/6/2012 | | DONE |
|
|
|
t/c w brodie - permit denied - needs to be picked up and resubmitted
|
Case Summary | | | 3/1/2012 | | DONE |
|
|
|
|
Application received | | | 3/1/2012 | | |
|
|
|
|