Miscellaneous action | | | 9/26/2012 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 8/31/2012 | 9/4/2012 | 9/4/2012 | A | PASS |
Forrest France
|
|
|
C/N items verified for completion. Fire alarm permit finaled.
|
INSP-Final Inspection | 5/14/2012 | 5/17/2012 | 5/17/2012 | A | FAIL |
Troy Cobbley
|
|
|
Smoke detector and manual pull station have been installed. Netcon was at an acceptable level of 5, all signals reported to central station. However, the alarm signals (pull station and water flow) did not intiate an audible alarm at the panel (required by NFPA 72 10.7). The smoke detector was not tested.
|
INSP-Final Inspection | 3/30/2012 | 4/2/2012 | 4/2/2012 | A | NR |
Forrest France
|
|
|
Existing system is not equipped with a MP or SD at the panel.
|
Issue and Print Permit | | | 3/22/2012 | | DONE |
Barbara Stitt
|
|
|
|
Plan assigned to (Stephanie) | 3/7/2012 | | 3/21/2012 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 3/21/2012 | | PASS |
|
|
|
|
Alarm Plan Check | 3/21/2012 | | 3/21/2012 | | PASS |
Stephanie L. Cobbley
|
|
|
Plans approved with review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 3/21/2012 | | DONE |
|
|
|
Approved plans available at front counter.
|
Inspection Record Card- Fire | 3/21/2012 | | 3/21/2012 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 3/21/2012 | | DONE |
|
|
|
t/c w bryan - permit ready and fees given
|
Permit Ready to Issue | | | 3/21/2012 | | DONE |
|
|
|
|
Application received | | | 3/7/2012 | | |
|
|
|
|