Permit NumberFIR12-00177
StatusFinaled
Name R M E INC
Site Address 5777 N MEEKER AVE
Project NameBODYBUILDING.COM
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to remove all fire alarm devices and wiring, installing a new FACP, pull station, and smoke detector above the panel, remote annunciator panel, and re-connecting the existing sprinkler monitoring. This scope of work includes HVAC monitoring/shutdown, freight elevator recall and shunt trip functions, and sprinkler system monitoring. A DSC communicator is being used instead of phone lines.
Associated building permit: BLD12-00412
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary  1/30/2014 DONE
INSP-Final Inspection8/14/20138/15/20138/15/2013APASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection8/13/20138/14/20138/14/2013AFAIL
DetailsTroy Cobbley
Basement fire alarm is complete (smoke detector was relocated and pull station lowered for my return trip). First floor fire alrm is complete (except updated as-builts are needed showing one additional in-duct detector). Second floor fire alarm is almost complete (Need to test all duct detectors, add two a/v's as marked on the plans)
CHANGE STATUS TO (ISS)  8/13/2013 DONE
DetailsChristina Prado
(F) Reprint permit  8/13/2013 DONE
Alarm Plan Check8/9/2013 8/9/2013 PASS
DetailsLee G Meredith
Plan modifications approved with redline comments on plans and matrix. All previous redlines and review comments still apply.
PLANS TAKEN FRONT DESK ALARM  8/9/2013 DONE
DetailsLee G Meredith
Approved plan modifications taken to front desk for processing.
Permit Ready to Issue  8/9/2013  
Inspection Record Card- Fire8/9/2013 8/9/2013 DONE
DetailsDarla L Downs
Telephone call  8/9/2013  
8-9-13 called RME permit ready
INSP-Alarm Testing8/6/20138/8/20138/8/2013AFAIL
DetailsTroy Cobbley
Inspection was for an elevator test but I could not perform the test since the monitoring was not set up yet. I then did a walk through of the first and second floors to verify a/v spacing. I found many a/v's are overspaced most of which were in the restrooms. Many a/v's are missing/have not been installed. The multiple rooms in the Kitchen Area are not built yet and notification has not been installed. The Copy Room has been changed into an office and the a/v deleted. Most of the 15cd a/v in the corridors are mounted above 10' which is too high. Per the installed 12 in-duct detectors have been added. The main elevator, per the contractor, is being "grand fathered" by the state of Idaho and will not be required to have recall as shown on the plans. I did not inspect the basement. Plan modifications are required prior to additional inspections and final sign off.
Plan resubmittals received  8/8/2013  
8-8-13 received 1 re-submittal checklist and 2 sets of plans sent to Lee M
FIR-Aging Inspection8/6/20138/6/20138/6/2013 NR
DetailsTroy Cobbley
work is in progress
FIR-Aging Inspection5/7/20135/7/20135/8/2013 NR
DetailsTroy Cobbley
Work is in progess
Plan assigned to (Stephanie)2/27/2013 3/6/2013 DONE
DetailsStephanie L. Cobbley
Alarm Plan Check3/6/2013 3/6/2013 PASS
DetailsStephanie L. Cobbley
Plan modifications approved with redlines and review comments.
PLANS TAKEN FRONT DESK ALARM  3/6/2013 DONE
Approved plan modifications taken to permit technician for processing
Permit Ready to Issue  3/6/2013 DONE
DetailsChristina Prado
Inspection Record Card- Fire3/6/2013 3/6/2013 DONE
DetailsChristina Prado
Telephone call  3/6/2013 DONE
DetailsChristina Prado
called Nathan to advise plan mod is ready and gave fees due
(F) Reprint permit  3/6/2013 DONE
CHANGE STATUS TO (ISS)  3/6/2013 DONE
DetailsTisha Gallop
Plan resubmittals received  2/27/2013 DONE
DetailsTisha Gallop
Plan Modification: Received two copies of application, submittal folder and plans; routed to SLC.
FIR-Aging Inspection2/5/20132/5/20132/13/2013 NR
DetailsTroy Cobbley
FIR-Aging Inspection9/28/20129/28/20129/28/2012 NR
DetailsTroy Cobbley
Per Clint the project is currently suspended but might possibly start back up.
Issue and Print Permit  4/18/2012 DONE
Plan assigned to (Stephanie)4/5/2012 4/16/2012 DONE
DetailsStephanie L. Cobbley
Alarm Plan Check4/16/2012 4/16/2012 PASS
DetailsStephanie L. Cobbley
Plans approved with redlines and review comments.
PLANS TAKEN FRONT DESK ALARM  4/16/2012 DONE
Inspection Record Card- Fire4/16/2012 4/16/2012 DONE
DetailsDarla L Downs
Telephone call  4/16/2012  
4-16-12 called Enterprise Electric permit ready and fee given ///dld
Permit Ready to Issue  4/16/2012  
Plan resubmittals received  4/12/2012 DONE
DetailsTisha Gallop
received application and two coipes submittal folder and plans; routed to Fire Review.
1st review completed  4/11/2012 FAIL
Alarm Plan Check4/11/2012 4/11/2012 FAIL
DetailsStephanie L. Cobbley
Plans denied - please see redlines and review comments.
Miscellaneous action  4/11/2012 DONE
faxed review comments to contractor
Miscellaneous action  4/11/2012 DONE
emailed fire alarm vendor per request to let him know that the plans are denied.
Miscellaneous action  4/11/2012 DONE
denied plans taken to front counter for contractor to pick up.
Application received  4/5/2012