Permit Information
Permit NumberFIR12-00181
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 5959 N DISCOVERY PL
Project NameYMCA West DH Addition
Customer Number 
ePlanReviewNo
Description
This quick permit is to provide two new door holders and four new smoke detectors to release doors upon activation. There are no written review comments. There is no associated building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  9/27/2012 DONE
plans taken to records for scanning
INSP-Final Inspection6/26/20126/26/20126/26/2012PPASS
DetailsTroy Cobbley
Permit finaled. Relay was repaired.
INSP-Final Inspection6/20/20126/26/20126/26/2012AFAIL
DetailsTroy Cobbley
The relay on the south side doors failed to operated when tested. The north side detectors and relay worked correctly.
Telephone call  6/12/2012 DONE
Curtis with Simplexgrinell called regarding smoke detector placement for door holder release. He stated that there is an air defuser located right by the door and wanted to know if the smoke detector could be offset from the centerline of the door. I told him code requires the detector to be on the center line, but reminded him that since the corridors have smoke detectors with normal corridor spacing that the smoke detector in question did not have to be within 5' of the door, so that should give him enough room to mount the detector at least 3' from the diffuser and still maintain the center line rule.
Telephone call  5/21/2012 DONE
Curtis with Simplexgrinnell called. He wanted to know if he could just provide as-built drawings to change the new door holders from the relay modules as submitted to instead tie them in to the existing door holder circuit. I told him he would need to submit a plan modification but to verify the doors are not part of a smoke control system and/or intended to close upon smoke detection in that corridor. If they are, then they can not change them to the existing door holder circuit (i.e. release on general alarm) because they would have to be released locally (i.e. smoke detector within 5' of the door).
Telephone call  5/21/2012 DONE
Curtis w/ Simplexgrinnell called back to let me know they are leaving things as submitted. He asked as a 'side note' if the could shut both sets of doors (one set at each end of the corridor) using one set of smoke detectors. I pointed him to 2010 NFPA 72 17.7.5.6.5.3 where it states that if the separation between doorways exceeds 24", each doorway shall be treated separately (i.e. one set of smoke detectors can not release both sets of doors).
Plan assigned to (Stephanie)4/9/2012 4/10/2012 DONE
DetailsStephanie L. Cobbley
1st review completed  4/10/2012 PASS
Alarm Plan Check4/10/2012 4/10/2012 PASS
DetailsStephanie L. Cobbley
Quick permit approved - no written review comments.
PLANS TAKEN FRONT DESK ALARM  4/10/2012 DONE
Approved quick permit plans available at front counter.
Inspection Record Card- Fire4/10/2012 4/10/2012 DONE
DetailsDarla L Downs
Permit Ready to Issue  4/10/2012  
Telephone call  4/10/2012  
4-10-12 called Dante permit ready and fee given ///dld
Issue and Print Permit  4/10/2012 DONE
DetailsTisha Gallop
Application received  4/9/2012