Permit Information
Permit NumberFIR12-00193
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 100 E IDAHO ST
Project NameBOISE MSTI PEDS PROCEDURE REMO
Customer Number 
ePlanReviewNo
Description
This quick permit scope of work is to add one strobe to a new procedure room. There are no written review comments. Approval is subject to field measurement of the EOL voltage drop. The voltage drop calculations are based on a 10% drop, therefore the minimum acceptable voltage is 21.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V (per UL 864, Standard for Control Units for Fire Signaling Systems). See NFPA 72 2010 Handbook 18.3.2.3 for further assistance with calculations.The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector. Associated building permit: BLD12-00537
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  6/4/2012 DONE
Plans taken to records for scanning.
INSP-Final Inspection5/14/20125/14/20125/14/2012PPASS
DetailsForrest France
Fire alarm work passed functional test. Permit finaled.
Issue and Print Permit  4/26/2012 DONE
DetailsBarbara Stitt
Plan assigned to (Stephanie)4/13/2012 4/16/2012 DONE
DetailsStephanie L. Cobbley
1st review completed  4/16/2012 PASS
Alarm Plan Check4/16/2012 4/16/2012 PASS
DetailsStephanie L. Cobbley
Quick permit approved - no written review comments.
PLANS TAKEN FRONT DESK ALARM  4/16/2012 DONE
Approved quick permit plans available at front counter.
Inspection Record Card- Fire4/16/2012 4/16/2012 DONE
DetailsDarla L Downs
Permit Ready to Issue  4/16/2012  
Telephone call  4/16/2012  
4-16-12 left message for Dante permit ready and fee given ///dld
Application received  4/13/2012