Permit Information
Permit NumberFIR12-00198
StatusFinaled
Name TRI STATE ELECTRIC
Site Address 455 S BROADWAY AVE
Project NameWalgreen's
Customer Number 
ePlanReviewNo
Description
8/29/12 PLAN MODIFICATION (1 initiating device affected): This plan modification is to incorporate building floorplan changes, relocate the fire alarm panel and related smoke detector from the sprinkler riser area to an electrical equipment room, and provide a second duct detector.
4-20-12: This fire alarm permit is to provide a sprinkler monitoring system and a voluntary manual fire alarm system. This scope of work includes a pull station, a smoke detector, a remote annunciator panel, monitoring for the sprinkler system, a duct detector for HVAC shutdown/monitoring, and notification throughout the building.
Associated building permit: BLD11-01696
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  11/30/2012 DONE
Plans taken to records for scanning.
INSP-Final Inspection10/5/201210/5/201210/5/2012PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection10/4/201210/5/201210/5/2012AFAIL
DetailsTroy Cobbley
Provide map at the facp with a legend so the responding fire dept. can interpret the map, provide as-built floor plan that is to scale (as the original submittal), provide NFPA 72 record of completion forms.
INSP-Final Inspection10/2/201210/4/201210/4/2012ANR
DetailsForrest France
Need to adjust cd setting at the electrical room, relocate one device at the pharmacy, provide as-built plans for added PIV and notification at the pharmacy, post map and signage at the FACP, provide record of inspection and testing report.
FIR-Aging Inspection10/2/201210/2/201210/3/2012 DONE
DetailsForrest France
Inspection scheduled 10/3.
CHANGE STATUS TO (ISS)  8/30/2012 DONE
DetailsTisha Gallop
Plan assigned to (Stephanie)8/23/2012 8/29/2012 DONE
DetailsStephanie L. Cobbley
Alarm Plan Check8/29/2012 8/29/2012 PASS
DetailsStephanie L. Cobbley
Plan modification approved with redlines and review comments.
PLANS TAKEN FRONT DESK ALARM  8/29/2012 DONE
Approved, redlined plan modification documents taken to permit technician for processing.
Inspection Record Card- Fire8/29/2012 8/29/2012 DONE
DetailsDarla L Downs
Permit Ready to Issue  8/29/2012  
Telephone call  8/29/2012  
8-29-12 called Daric- Tri State Electric permit ready and fee given ///dld
Plan resubmittals received  8/23/2012 DONE
DetailsChristina Prado
***Plan Mod*** Received two new sets of plans; calcs; battery calcs; voltage calcs and one new application and checklist document. Gave to Stephanie for further review
Issue and Print Permit  5/17/2012 DONE
DetailsTisha Gallop
Telephone call  4/23/2012  
4-23-12 called Tri State Electric permit ready and fee given ///dld
Plan assigned to (Stephanie)4/16/2012 4/20/2012 DONE
DetailsStephanie L. Cobbley
Telephone call  4/20/2012 DONE
Spoke with the fire alarm designer to get clarification on ceiling and racking heights. He stated the general sales racks do not exceed 5' and the ceilings are 15'. In the pharmacy area, the racks/storage are 7' and the ceilings are 9'. I let him know additional devices would be required in the pharmacy to provide adequate coverage.
1st review completed  4/20/2012 PASS
Alarm Plan Check4/20/2012 4/20/2012 PASS
DetailsStephanie L. Cobbley
Approved with redlines and review comments.
PLANS TAKEN FRONT DESK ALARM  4/20/2012 DONE
Approved redlined plans available at front counter.
Inspection Record Card- Fire4/20/2012 4/20/2012 DONE
DetailsDarla L Downs
Permit Ready to Issue  4/20/2012  
Application received  4/16/2012