Permit Information
Permit NumberFIR12-00228
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 1253 N COLE RD
Project NamePEACE IN JESUS LUTHERAN CHURCH
Customer Number 
ePlanReviewNo
Description
7/20/12 PLAN MODIFICATION (no initiating devices affected): This plan modification is to replace the DACT with a DSC wireless monitor – see additional notes starting on page 5)
6/26/12: This fire alarm permit is to replace the existing fire alarm panel with new, provide an annunciator panel, relocate the existing NAC remote power supply, provide a new smoke detector above the FACP, and add and/or relocate notification to accommodate a tenant remodel. This scope of work includes monitoring an existing sprinkler system, existing duct detectors for HVAC monitoring/shutdown, and providing full notification.
Associated building permit: BLD12-00282
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  9/26/2012 DONE
Plans taken to records for scanning.
INSP-Final Inspection8/3/20128/3/20128/3/2012PPASS
DetailsTroy Cobbley
Permit finaled. Map at annunciator to be posted by 5:00pm
INSP-Final Inspection8/1/20128/3/20128/3/2012AFAIL
DetailsTroy Cobbley
Provide the city approved plan modifications, provide testing of the three non-functional hvac units and correct the spacing of the two audio/visual devices.
Issue and Print Permit  7/24/2012 DONE
Plan assigned to (Stephanie)7/12/2012 7/20/2012 DONE
DetailsStephanie L. Cobbley
Alarm Plan Check7/20/2012 7/20/2012 PASS
DetailsStephanie L. Cobbley
Plan modification approved with redlines and written review comments.
PLANS TAKEN FRONT DESK ALARM  7/20/2012 DONE
Approved redlined plan modification documents taken to permit technician for processing.
Inspection Record Card- Fire7/20/2012 7/20/2012 DONE
DetailsDarla L Downs
Permit Ready to Issue  7/20/2012  
Telephone call  7/20/2012  
7-20-12 called Tara-Simplex Grinnell permit ready and fee given ///dld
Plan resubmittals received  7/12/2012 DONE
DetailsTisha Gallop
received two copies of application, submittal folder and plans; routed to Fire Review.
Issue and Print Permit  6/29/2012 DONE
Plan assigned to (Stephanie)5/2/2012 6/26/2012 DONE
DetailsStephanie L. Cobbley
Alarm Plan Check6/26/2012 6/26/2012 PASS
DetailsStephanie L. Cobbley
Plans approved with redlines and review comments.
PLANS TAKEN FRONT DESK ALARM  6/26/2012 DONE
Approved redlined plans available at front counter.
Inspection Record Card- Fire6/26/2012 6/26/2012 DONE
DetailsDarla L Downs
Permit Ready to Issue  6/26/2012  
Telephone call  6/26/2012  
6-26-12 called Dante- Simplex Grinnell permit ready and fee given ///dld
Plan resubmittals received  6/19/2012 DONE
DetailsChristina Prado
Resubmittals received 6/19/12. Received two sets of plans; applications; checklists and calcs. Given to Stephanie for review
Miscellaneous action  5/24/2012 DONE
DetailsTisha Gallop
contractor picked up denied plans
Telephone call  5/21/2012 DONE
Spoke with Dante at Simplexgrinnell. He stated that they were going to replace the panel with one that can accomodate a remote annunciator. I let him know that I would need to deny the plans and have them resubmit.
Alarm Plan Check5/21/2012 5/21/2012 FAIL
DetailsStephanie L. Cobbley
Contractor is changing the fire alarm panel, therefore the plans must be resubmitted. There are no written review comments, as they will change depending on the type of panel submitted.
Miscellaneous action  5/21/2012 DONE
Emailed the fire alarm contractor to let them know they could pick up their original set of drawings from the permit counter. There are no redlines or review comments at this time due to the contractor deciding to replace the panel.
1st review completed  5/16/2012 FAIL
Awaiting direction from the contractor regarding the annunciator
Miscellaneous action  5/15/2012 DONE
Adam with Simplexgrinnel stopped by my office to let me know that they have given a proposal to the owner and should have an answer by Thursday, 5/17/12 on what direction they will be taking with the annunciator panel.
Telephone call  5/11/2012 DONE
Dante with Simplexgrinnell called to let me know that they have given the information to the owner and are awaiting an answer from them regarding the annunciator.
Telephone call  5/9/2012 DONE
Dante with Simplexgrinnell called regarding another project. When I answered his question, I asked him if he recieved my email regarding the annunciator. He said he had not seen it, so I re-emailed it to him.
Miscellaneous action  5/8/2012 DONE
Sent an email to Dante F. and Charlie B. at Simplexgrinnell stating that an annunciator panel is required at the front entrance. The FACP has been moved to a room not in view of the front entry. Per our ordinance, this prompts the requirement for placing a remote annunciator at the main entrance to the building. I asked them to please provide either; a data sheet for the compatible annunciator , a revised matrix to include annunciation at the remote annunciator, and revised battery calculations; or a statement that the FACP will be relocated to the main entrance.
Application received  5/2/2012  
Case Summary  5/2/2012 DONE