Miscellaneous action | | | 2/14/2013 | | DONE |
|
|
|
Plans taken to records for scanning
|
INSP-Final Inspection | 2/12/2013 | 2/13/2013 | 2/13/2013 | P | PASS |
Forrest France
|
|
|
Remainder of fire alarm testing completed and passed after noted correction items finished. Permit finaled.
|
INSP-Final Inspection | 2/8/2013 | 2/11/2013 | 2/11/2013 | A | PART |
Forrest France
|
|
|
Items needed for final include; points map with accurate room numbers, correct addresses at SD 60 and 63, revise visual coverage at corridor 145- see red line review comments, install panel batteries per plans. ID and duct detectors not yet tested. Remainder of installation including riser supervision, notification, initiating, monitoring and panel items tested okay.
|
(F) Reprint permit | | | 1/31/2013 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 1/31/2013 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 1/10/2013 | | 1/23/2013 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | 1/23/2013 | | 1/23/2013 | | PASS |
Stephanie L. Cobbley
|
|
|
2nd Plan modification approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 1/23/2013 | | DONE |
|
|
|
Approved redlined plans taken to permit technician for processing.
|
Telephone call | | | 1/23/2013 | | DONE |
|
|
|
called Jason to advise plan mod #2 is ready
|
Permit Ready to Issue | | | 1/23/2013 | | DONE |
Christina Prado
|
|
|
|
Inspection Record Card- Fire | 1/23/2013 | | 1/23/2013 | | DONE |
Christina Prado
|
|
|
|
Plan resubmittals received | | | 1/10/2013 | | |
|
|
|
Plan modification
|
FIR-Aging Inspection | 11/16/2012 | 11/16/2012 | 11/16/2012 | | DONE |
Forrest France
|
|
|
Site work in progress.
|
CHANGE STATUS TO (ISS) | | | 11/15/2012 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 10/17/2012 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 10/8/2012 | | 10/16/2012 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | 10/16/2012 | | 10/16/2012 | | PASS |
Stephanie L. Cobbley
|
|
|
Plan modifications approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 10/16/2012 | | DONE |
|
|
|
Approved plan modifications taken to permit technician for processing.
|
Permit Ready to Issue | | | 10/16/2012 | | DONE |
Tisha Gallop
|
|
|
|
Inspection Record Card- Fire | 10/16/2012 | | 10/16/2012 | | DONE |
Tisha Gallop
|
|
|
|
Plan resubmittals received | | | 10/8/2012 | | DONE |
|
|
|
Plan Modification: Received application and two copies of submittal folder and plans; routed to Fire.
|
Telephone call | | | 9/24/2012 | | DONE |
|
|
|
Jason with AEI called regarding multiple changes to the fire alarm due to changes in the buildng plan layout. He asked if he needed to re-submit the issued plans prior to making the changes in the field. I told him that he could do the work under his issued permit, but that he would need to submit a plan modification and get approval prior to calling for a final inspection.
|
Issue and Print Permit | | | 7/5/2012 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 5/22/2012 | | 7/3/2012 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | 7/3/2012 | | 7/3/2012 | | PASS |
Stephanie L. Cobbley
|
|
|
Plans approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 7/3/2012 | | DONE |
|
|
|
Approved redlined plans taken to permit technician for processing.
|
Inspection Record Card- Fire | 7/3/2012 | | 7/3/2012 | | DONE |
Darla L Downs
|
|
|
|
Permit Ready to Issue | | | 7/3/2012 | | |
|
|
|
|
Telephone call | | | 7/3/2012 | | |
|
|
|
7-3-12 called Jason- Audio Electronics permit ready and fee given ///dld
|
Plan resubmittals received | | | 6/26/2012 | | |
|
|
|
|
1st review completed | | | 5/30/2012 | | FAIL |
|
|
|
|
Alarm Plan Check | 5/30/2012 | | 5/30/2012 | | FAIL |
Stephanie L. Cobbley
|
|
|
Plans denied - see redlines and review comments.
|
Miscellaneous action | | | 5/30/2012 | | DONE |
|
|
|
Faxed review comments to applicant.
|
Miscellaneous action | | | 5/30/2012 | | DONE |
|
|
|
Denied plans and review comments available at front counter.
|
Application received | | | 5/22/2012 | | |
|
|
|
|