Permit Information
Permit NumberFIR12-00255
StatusFinaled
Name AUDIO ELECTRONICS INC
Site Address 3550 W AMERICANA TERR
Project NameBoise Skilled Nursing
Customer Number 
ePlanReviewNo
Description
1/23/13 Plan Modification (11 initiating devices affected): This plan modification is to provide additional smoke detectors due to beam locations and other building floor plan changes and to add release for magnetic door holders.
10/16/12 Plan Modification (7 initiating devices affected): This plan modification is to incorporate field changes to the fire alarm plan, provide additional smoke detectors due to beams, as well as reflect building plan changes.
7/3/12: This fire alarm permit is to provide a new manual and automatic fire alarm system in a new building. This scope of work includes a remote annunciator panel, sprinkler system monitoring (wet and dry system), hood suppression system monitoring, pull stations, smoke detectors, notification, in-duct detectors for f/s damper shutdown, and duct detectors for HVAC shutdown/monitoring, and magnetic door lock releasing functions.
Associated building permit: BLD11-00021
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  2/14/2013 DONE
Plans taken to records for scanning
INSP-Final Inspection2/12/20132/13/20132/13/2013PPASS
DetailsForrest France
Remainder of fire alarm testing completed and passed after noted correction items finished. Permit finaled.
INSP-Final Inspection2/8/20132/11/20132/11/2013APART
DetailsForrest France
Items needed for final include; points map with accurate room numbers, correct addresses at SD 60 and 63, revise visual coverage at corridor 145- see red line review comments, install panel batteries per plans. ID and duct detectors not yet tested. Remainder of installation including riser supervision, notification, initiating, monitoring and panel items tested okay.
(F) Reprint permit  1/31/2013 DONE
CHANGE STATUS TO (ISS)  1/31/2013 DONE
Plan assigned to (Stephanie)1/10/2013 1/23/2013 DONE
DetailsStephanie L. Cobbley
Alarm Plan Check1/23/2013 1/23/2013 PASS
DetailsStephanie L. Cobbley
2nd Plan modification approved with redlines and review comments.
PLANS TAKEN FRONT DESK ALARM  1/23/2013 DONE
Approved redlined plans taken to permit technician for processing.
Telephone call  1/23/2013 DONE
called Jason to advise plan mod #2 is ready
Permit Ready to Issue  1/23/2013 DONE
DetailsChristina Prado
Inspection Record Card- Fire1/23/2013 1/23/2013 DONE
DetailsChristina Prado
Plan resubmittals received  1/10/2013  
Plan modification
FIR-Aging Inspection11/16/201211/16/201211/16/2012 DONE
DetailsForrest France
Site work in progress.
CHANGE STATUS TO (ISS)  11/15/2012 DONE
CHANGE STATUS TO (ISS)  10/17/2012 DONE
Plan assigned to (Stephanie)10/8/2012 10/16/2012 DONE
DetailsStephanie L. Cobbley
Alarm Plan Check10/16/2012 10/16/2012 PASS
DetailsStephanie L. Cobbley
Plan modifications approved with redlines and review comments.
PLANS TAKEN FRONT DESK ALARM  10/16/2012 DONE
Approved plan modifications taken to permit technician for processing.
Permit Ready to Issue  10/16/2012 DONE
DetailsTisha Gallop
Inspection Record Card- Fire10/16/2012 10/16/2012 DONE
DetailsTisha Gallop
Plan resubmittals received  10/8/2012 DONE
Plan Modification: Received application and two copies of submittal folder and plans; routed to Fire.
Telephone call  9/24/2012 DONE
Jason with AEI called regarding multiple changes to the fire alarm due to changes in the buildng plan layout. He asked if he needed to re-submit the issued plans prior to making the changes in the field. I told him that he could do the work under his issued permit, but that he would need to submit a plan modification and get approval prior to calling for a final inspection.
Issue and Print Permit  7/5/2012 DONE
Plan assigned to (Stephanie)5/22/2012 7/3/2012 DONE
DetailsStephanie L. Cobbley
Alarm Plan Check7/3/2012 7/3/2012 PASS
DetailsStephanie L. Cobbley
Plans approved with redlines and review comments.
PLANS TAKEN FRONT DESK ALARM  7/3/2012 DONE
Approved redlined plans taken to permit technician for processing.
Inspection Record Card- Fire7/3/2012 7/3/2012 DONE
DetailsDarla L Downs
Permit Ready to Issue  7/3/2012  
Telephone call  7/3/2012  
7-3-12 called Jason- Audio Electronics permit ready and fee given ///dld
Plan resubmittals received  6/26/2012  
1st review completed  5/30/2012 FAIL
Alarm Plan Check5/30/2012 5/30/2012 FAIL
DetailsStephanie L. Cobbley
Plans denied - see redlines and review comments.
Miscellaneous action  5/30/2012 DONE
Faxed review comments to applicant.
Miscellaneous action  5/30/2012 DONE
Denied plans and review comments available at front counter.
Application received  5/22/2012