Permit Information
Permit NumberFIR12-00260
StatusFinaled
Name ALARM SYSTEMS INTEGRATION INC
Site Address 11911 W USTICK RD
Project NameLittle Tigers Daycare
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to install a manual fire alarm system and a complete coverage automatic smoke detection system. This permit scope of work includes pull stations at every exit, smoke detectors in accordance with NFPA 72 total coverage instead of the single-station/multi-station alarms required by ordinance for childcare, full notification, and a remote annunciator panel. Heat detectors are being used in kitchen areas.
Associated building permit: BLD12-01449
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary  6/3/2016 DONE
INSP-Final Inspection6/18/20156/19/20156/19/2015APASS
DetailsJim Page
Previuos noted items corrected, fire system inspection passed/complete
INSP-Alarm Testing6/17/20156/18/20156/18/2015AFAIL
DetailsTroy Cobbley
Todays inspection was for the new addition. Smoke detectors did not alarm at the panel, Panel did not receive trouble signal from new addition. Smoke detectors to be mounted atleast 3'-0" from ceiling fans. I stopped testing until issues have been resolved.
Override - Parcel Holds6/18/20151/1/19006/18/2015  
Fire final ONLY
INSP-Final Inspection6/16/20156/17/20156/17/2015ACANC
DetailsTroy Cobbley
Jack Phone #: ###-####
Override - Parcel Holds6/16/20151/1/19006/16/2015  
Fire final ONLY
FIR-Aging Inspection6/10/20156/10/20156/10/2015 NR
DetailsTroy Cobbley
It appears that work is in progress based on footing inspections.
INSP-Final Inspection5/20/20135/20/20135/20/2013APART
DetailsTroy Cobbley
Temporary occupancy approved by building official per approval of plan modifications. The applicant has requested a TCO due to the addition not being completed. The estimated completeion date of the addition is within 360 days or sooner per the applicant.
INSP-Final Inspection5/13/20135/14/20135/14/2013AFAIL
DetailsTroy Cobbley
All work has been completed, inspected and tested up to the existing south wall. The gym and related restrooms have not been costructed yet. Two smoke detectors were relocated as I waited. Will need as-builts showing the closets where additional smoke detectors had to be added.
Permit Ready to Issue  4/24/2013  
Inspection Record Card- Fire4/24/2013 4/24/2013 DONE
DetailsDarla L Downs
Telephone call  4/24/2013  
4-24-13 called Alarm Systems permit ready and fee given ///dld
Issue and Print Permit  4/24/2013 DONE
Plan assigned to (Stephanie)5/23/2012 4/23/2013 DONE
DetailsStephanie L. Cobbley
Alarm Plan Check4/23/2013 4/23/2013 PASS
DetailsStephanie L. Cobbley
Plans approved with review comments.
PLANS TAKEN FRONT DESK ALARM  4/23/2013 DONE
Approved plans taken to permit technician for processing.
Telephone call  4/22/2013 DONE
DetailsScott Arellano
Spoke with Tammy Morris this morning and updated her on what the City needs from the permit applicant. I Let her know that once we get the updated plans showing the additional detection devices within the closets and other items mentioned in the plan reviewer correspondence, we’ll can issue the permit and get the ball rolling.
Plan resubmittals received  4/22/2013 DONE
DetailsTisha Gallop
received small documents and two copies of plans; routed to Fire.
Miscellaneous action  4/18/2013 DONE
Can't complete review of re-submittals. I sent an email to the applicant stating that he indicated in the scope of work that the intent is non-required complete smoke detector coverage instead of the single/multi station smoke alarms. This is definitely acceptable, however complete smoke detector coverage includes all closets, etc... so there is a need to provide additional detectors. I provided the NFPA code sections regarding this issue. In addition, in my previous reviews and in conversations since, I explained that I would not approve the DMP XR100N internet communications method for use in the City of Boise. I have also discussed this with our fire marshal and he agrees that the internet communications method provided by the DMP is not an acceptable choice for many reasons including because the owner can change the internet provider at will. I provided a list of approved communications technologies with my previous review comments, however the one-line diagram and submittal packet have not been changed to reflect which approved method hase been chosen. I let him know that rather than reject the submittals a third time and incur additional review fees, I am willing to wait to reject the plans if he can have replacement submittal packets to me by Tuesday, 4/23/13. I asked him to please provide smoke detectors in all areas required for complete coverage and indicate which approved method of communication is to be used. I attached another copy of the approved communications methods in the email. All other redlines seem to have been implemented and/or clarified satisfactorily.
Plan resubmittals received  4/12/2013  
4-12-13 received 2 sets of applications & plans sent to SLC
Miscellaneous action  3/12/2013 DONE
Emailed Jack with Alarm Systems Integration to get clarification on the network communications.
Miscellaneous action  3/12/2013 DONE
Received an email from Jack with answers to my questions. One of the answers was that the user/owner would have freedom of selection of internet providers. I emailed Jack letting him know the internet communications submitted would not be permitted and that the plans would be denied due to this and other factors.
Alarm Plan Check3/12/2013 3/12/2013 FAIL
DetailsStephanie L. Cobbley
re-submittals denied
Miscellaneous action  3/12/2013 DONE
Faxed review comments/denial letter to applicant. Denied plans taken to the drawer at the permit desk.
Plan resubmittals received  3/6/2013 DONE
Plan assigned to (Stephanie)3/6/2013 3/6/2013 DONE
DetailsStephanie L. Cobbley
1st review completed  5/31/2012 FAIL
Alarm Plan Check5/31/2012 5/31/2012 FAIL
DetailsStephanie L. Cobbley
Plans denied due to incomplete application - no building permit has been indicated. Per PRE12-00120, there is a permit pending. Plans must be resubmitted after a building permit has been issued. No written review comments. No review done at this time.
Telephone call  5/31/2012 DONE
Spoke with Alarm Systems Integration to let them know the plans are being denied and that no review has been done since there is no building permit yet. He asked if he could leave the plans at the city and just wait for the building permit to be issued. I said that I would put them in the drawer up at the permit desk and that he doesn't technically have to pick them up but it is recommended because there may be changes to the layout during the planning and building review stages. He stated that he understands.
Miscellaneous action  5/31/2012 DONE
Denied plans taken to the front counter.
Application received  5/23/2012