Information based on query as of Tuesday, September 17, 2024.
Permit Information
Permit NumberFIR12-00266
StatusFinaled
Name CURTIS FIRE SPRINKLER SERVICE INC
Site Address 12542 W FAIRVIEW AVE
Project NameSOCKEYE BREW PUB SHELL
Customer Number 
ePlanReviewNo
Description
The Fire Sprinkler Scope of work consists of 6”x24’± of underground through a 4” backflow preventer to a 4” header. The header has a3” wet system and a 2½” dry system. The dry system supplies the outside canopy. The tree type wet system has a 3” main with telescoping branch piping. The building for the most part has exposed open wood joist construction. The building will be used a combinations distillery and restaurant
Contractor’s Note:
The building permit has not been issued at this time. The building department may determine that changes are required to the building plans in order to meet code. The changes may affect the sprinkler system. The sprinkler contractor will be obligated to make all necessary changes that may be required. Therefore, if the sprinkler contractor chooses to proceed without an issued building permit, they will do so on their own cognizance. This note does not constitute an early start agreement.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  10/11/2012 DONE
DetailsTim Frost
Sent to Records for scanning.
INSP-Final Inspection9/12/20129/12/20129/12/2012PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection9/10/20129/11/20129/12/2012PFAIL
DetailsTroy Cobbley
Provide pressure relief valve. Forward flush passed.
INSP-Sprinkler Rough-in/Hydro8/22/20128/22/20128/22/2012PPASS
DetailsTroy Cobbley
wet system hydro passed
INSP-Sprinkler Rough-in/Hydro8/21/20128/21/20128/21/2012PFAIL
DetailsTroy Cobbley
The wet system hydro test failed due to visable pressure loss at the guage. Sprinkler coverage has been provided in the future kitchen area and pendant heads have been modified as discussed in the future restraunt restrooms.
INSP-Sprinkler Rough-in8/13/20128/13/20128/13/2012PPASS
DetailsTroy Cobbley
Overhead/hydrostatic test for both wet and dry systems passed.
Issue and Print Permit  8/9/2012 DONE
Miscellaneous action  8/8/2012 DONE
Field inspector during conference found fp piping installed before the permit was issued. Therefore, a double fee will apply.
Field inspector informed owner that the racking that was installed would required a racking permit since it is > 8' high. Field inspector also informed owner to remove all commodity from racks until an OC has been issured.
Sprinkler Plan Check6/6/2012 6/6/2012 PASS
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
PLANS/APPL TAKEN TO FRONT DESK  6/6/2012 DONE
DetailsTim Frost
Inspection Record Card- Fire6/6/2012 6/6/2012 DONE
DetailsDarla L Downs
Permit Ready to Issue  6/6/2012  
Telephone call  6/6/2012  
6-6-12 called (Don) Curtis Fire Sprinkler permit ready and fee given ///dld
Plan assigned to (Tim)5/25/2012 6/6/2012 DONE
DetailsTim Frost
Plan resubmittals received  6/5/2012  
DetailsTim Frost
Miscellaneous action  5/31/2012 DONE
DetailsTisha Gallop
Curtis Fire picked up denied plans
Sprinkler Plan Check5/30/2012 5/30/2012 FAIL
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
1st review completed  5/30/2012 FAIL
DetailsTim Frost
Miscellaneous action  5/30/2012 DONE
DetailsTim Frost
Emailed review to contractor
Telephone call  5/30/2012  
5-30-12 called (Don) Curtis Fire Sprinkler permit ready for pick up///dld
Plan resubmittals received  5/29/2012 DONE
DetailsChristina Prado
Received three new sets of plans marked FP-1. Gave to Tim for further review
Application received  5/25/2012