Miscellaneous action | | | 10/11/2012 | | DONE |
Tim Frost
|
|
|
Sent to Records for scanning.
|
INSP-Final Inspection | 8/3/2012 | 8/3/2012 | 8/3/2012 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Sprinkler Rough-in | 7/10/2012 | 7/10/2012 | 7/10/2012 | P | PASS |
Troy Cobbley
|
|
|
Sprinkler piping can be covered.
|
INSP-Conference | 7/9/2012 | 7/10/2012 | 7/10/2012 | A | DONE |
Troy Cobbley
|
|
|
Sprinkler piping is ok to cover.
|
INSP-Conference | 7/9/2012 | 7/9/2012 | 7/9/2012 | P | DONE |
Troy Cobbley
|
|
|
Ceiling is ok to install from the west wall to the first column line.
|
INSP-Final Inspection | 7/9/2012 | 7/9/2012 | 7/9/2012 | P | FAIL |
Troy Cobbley
|
|
|
Inspection was actually a conference on what is required to fix the insulation blocking the upright sprinkler heads. We went over the NFPA 13 obstruction charts.
|
INSP-Sprinkler Rough-in | 7/3/2012 | 7/5/2012 | 7/5/2012 | A | PART |
Troy Cobbley
|
|
|
Upright coverage has been added but the insulation blockage issue has not been addressed yet. Piping can not be covered yet.
|
INSP-Sprinkler Rough-in | 6/27/2012 | 6/28/2012 | 6/28/2012 | A | PART |
Troy Cobbley
|
|
|
Rough-in, for pendant sprinklers, for the most part is ok. Almost all of the upright sprinklers are blocked by hanging insulation. Also Mike and I found one location where upright heads are overspaced from an existing wall and some of the existing upright heads are blocked by duct work. These two items will need to be addressed prior to an approval for cover being given.
|
Issue and Print Permit | | | 6/11/2012 | | DONE |
|
|
|
|
Plan assigned to (Tim) | 5/30/2012 | | 6/5/2012 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 6/5/2012 | | 6/5/2012 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/5/2012 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 6/5/2012 | | 6/5/2012 | | DONE |
Darla L Downs
|
|
|
|
Permit Ready to Issue | | | 6/5/2012 | | |
|
|
|
|
Telephone call | | | 6/5/2012 | | |
|
|
|
6-5-12 called (Tom) Shilo Automatic Sprinkler permit ready and fee given ///dld
|
Plan resubmittals received | | | 6/1/2012 | | DONE |
Christina Prado
|
|
|
received three sets of response letter, application, checklist, specs and plans marked FP-1. Routed to Tim Frost for further review
|
Sprinkler Plan Check | 5/31/2012 | | 5/31/2012 | | FAIL |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 5/31/2012 | | FAIL |
Tim Frost
|
|
|
|
Telephone call | | | 5/31/2012 | | |
|
|
|
5-31-12 called Shilo Automatic Sprinkler let message for Tom permit ready for pick up///dld
|
Application received | | | 5/30/2012 | | |
|
|
|
|