Miscellaneous action | | | 9/26/2012 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 9/19/2012 | 9/19/2012 | 9/19/2012 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 9/17/2012 | 9/19/2012 | 9/19/2012 | A | FAIL |
Troy Cobbley
|
|
|
Provide the correct as-builts, updated map and the correct NFPA 72 record of completion forms.
|
INSP-Final Inspection | 9/10/2012 | 9/11/2012 | 9/11/2012 | P | FAIL |
Troy Cobbley
|
|
|
None of the addressing on the city approved plans matches the actual installed addresses. Also after testing was completed I found the the monitoring account had not been set up and no signals had been received by the monitoring station. The hi/low pressure switch has been programed for alarm and not the required supervisory signal. A map at the facp has not been provided yet. Teh manual pull station was mounted too high but was lowered prior to my leaving the job site.. Phone lines tested ok. Entire system will need to be retested when the monitoring account has been set up.
|
Issue and Print Permit | | | 8/27/2012 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 6/1/2012 | | 8/16/2012 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | 8/16/2012 | | 8/16/2012 | | PASS |
Stephanie L. Cobbley
|
|
|
Resubmittal approved with review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 8/16/2012 | | DONE |
|
|
|
Approved plans taken to permit technician for processing.
|
Telephone call | | | 8/16/2012 | | DONE |
Christina Prado
|
|
|
called Kytia to advise permit is ready
|
Permit Ready to Issue | | | 8/16/2012 | | DONE |
Christina Prado
|
|
|
|
Inspection Record Card- Fire | 8/16/2012 | | 8/16/2012 | | DONE |
Christina Prado
|
|
|
|
Plan resubmittals received | | | 8/13/2012 | | |
|
|
|
8-13-12 received 2 revised sets of plans and applications sent to fire.
|
1st review completed | | | 6/12/2012 | | FAIL |
|
|
|
|
Alarm Plan Check | 6/12/2012 | | 6/12/2012 | | FAIL |
Stephanie L. Cobbley
|
|
|
Plans denied - can not complete review because the occupant load has not been calculated by the building official. In addition, this permit must be attached to a tenant improvement permit, which has not yet been submitted. Because the estimated occupant load is close to or over 300, the plans must either wait to be resubmitted after the building official has calculated the occupant load, or must be resubmitted with a manual fire alarm system. No written review comments have been done at this time.
|
Miscellaneous action | | | 6/12/2012 | | DONE |
|
|
|
An email was sent to the applicant letting them know the plans are denied and that one of their sets of submittals is available at the front counter for them to pick up.
|
Telephone call | | | 6/12/2012 | | DONE |
|
|
|
Called the applicant and left a message the plans are denied.
|
Miscellaneous action | | | 6/12/2012 | | DONE |
|
|
|
Denied plans available at front counter for applicant to pick up.
|
Application received | | | 6/1/2012 | | DONE |
Barbara Stitt
|
|
|
|