Miscellaneous action | | | 11/30/2012 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 10/3/2012 | 10/4/2012 | 10/4/2012 | A | PASS |
Forrest France
|
|
|
Remainder of work passed inspection. Fire alarm permit finaled.
|
INSP-Final Inspection | 9/12/2012 | 9/13/2012 | 9/13/2012 | P | FAIL |
Forrest France
|
|
|
Refer to fire code review notes items number 14,15 and 23. Also need to test elevator recall functions when car is operational.
|
INSP-Alarm Testing | 9/5/2012 | 9/5/2012 | 9/5/2012 | P | PART |
Forrest France
|
|
|
Regarding fire door operations and releasing mechanism per NFPA 80.
|
INSP-Alarm Testing | 8/9/2012 | 8/9/2012 | 8/9/2012 | P | PART |
Forrest France
|
|
|
Regarding duct detectors for units below 2000 cfm.
|
Plan assigned to (Stephanie) | 6/8/2012 | | 7/19/2012 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | 7/19/2012 | | 7/19/2012 | | PASS |
Stephanie L. Cobbley
|
|
|
Resubmittals approved with review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 7/19/2012 | | DONE |
|
|
|
Approved plans taken to permit technician for processing.
|
Inspection Record Card- Fire | 7/19/2012 | | 7/19/2012 | | DONE |
Darla L Downs
|
|
|
|
Permit Ready to Issue | | | 7/19/2012 | | |
|
|
|
|
Telephone call | | | 7/19/2012 | | |
|
|
|
7-19-12 called- permit ready and fee given ///dld
|
Issue and Print Permit | | | 7/19/2012 | | DONE |
Barbara Stitt
|
|
|
|
Telephone call | | | 7/18/2012 | | DONE |
|
|
|
Jason with AEI called to let me know the sprinkler contractor met an exception and did not have to install the foam system. He asked if I could just use the previously submitted plans that were never picked up as the resubmittals. I agreed.
|
Plan resubmittals received | | | 7/18/2012 | | DONE |
Christina Prado
|
|
|
Received two new sets of plans, checklist and applications. Routed to Stephanie for review
|
1st review completed | | | 6/13/2012 | | FAIL |
|
|
|
|
Alarm Plan Check | 6/13/2012 | | 6/13/2012 | | FAIL |
Stephanie L. Cobbley
|
|
|
Plans denied - possible sprinkler foam system requirements may change the fire alarm plans.
|
Telephone call | | | 6/13/2012 | | DONE |
|
|
|
Spoke to Jason at AEI and let him know about the issues with the sprinkler permit being denied in part due to possible foam system requirements that would change the number of valves to be monitored by the fire alarm system. I let him know that I could approve the plans but that if the sprinkler reviewer determines a foam system is required then a fire alarm plan modification would be required. He opted to have me reject the fire alarm plans instead and said he would just wait until the sprinkler review items have been addressed.
|
Miscellaneous action | | | 6/13/2012 | | DONE |
|
|
|
faxed the review notes to AEI
|
Miscellaneous action | | | 6/13/2012 | | DONE |
|
|
|
Emailed Jason letting him know he can pick up his denied plans at the front counter at his convenience.
|
Application received | | | 6/8/2012 | | |
|
|
|
|