Miscellaneous action | | | 9/26/2012 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 7/11/2012 | 7/11/2012 | 7/12/2012 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
Miscellaneous action | | | 7/11/2012 | | DONE |
|
|
|
Received as-built drawings
|
INSP-Final Inspection | 7/9/2012 | 7/10/2012 | 7/10/2012 | A | FAIL |
Troy Cobbley
|
|
|
To final this permit the inoperative hvac unit needs to be repaired and all four of the hvac units needs to shutdown immediately upon detection of smoke. They currently shut down after several minutes. As-builts are needed showing the changes.
|
Issue and Print Permit | | | 7/9/2012 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 6/11/2012 | | 7/6/2012 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Telephone call | | | 7/6/2012 | | DONE |
|
|
|
Spoke to Keith w/ Vanguard and requested revised battery calculations and voltage drops because they were inconsistent with the plans.
|
Miscellaneous action | | | 7/6/2012 | | DONE |
|
|
|
Received revised battery calculations and voltage drops.
|
Miscellaneous action | | | 7/6/2012 | | DONE |
|
|
|
Sent Keith w/Vanguard an email requesting re-revised battery calculations and voltage drops. The ones he emailed still had one revision from the plans that was not reflected in the calcs/voltage drops.
|
Miscellaneous action | | | 7/6/2012 | | DONE |
|
|
|
Received re-revised battery calculations and voltage drops.
|
Alarm Plan Check | 7/6/2012 | | 7/6/2012 | | PASS |
Stephanie L. Cobbley
|
|
|
Plans approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 7/6/2012 | | DONE |
|
|
|
Approved redlined plans taken to permit technician for processing.
|
Inspection Record Card- Fire | 7/6/2012 | | 7/6/2012 | | DONE |
Darla L Downs
|
|
|
|
Permit Ready to Issue | | | 7/6/2012 | | |
|
|
|
|
Telephone call | | | 7/6/2012 | | |
|
|
|
7-6-12 called Vanguard Fire- left message permit ready and fee given///dld
|
Plan resubmittals received | | | 6/29/2012 | | DONE |
Christina Prado
|
|
|
Received two copies of new plans, applications, plan review notes, calcs and one new checklist. Gave to Stephanie for further review
|
Alarm Plan Check | 6/25/2012 | | 6/25/2012 | | FAIL |
Stephanie L. Cobbley
|
|
|
Plans denied - see redlines and review comments.
|
Miscellaneous action | | | 6/25/2012 | | DONE |
|
|
|
Emailed applicant to let them know the plans have been denied and that they can pick up the review comments and redlined plans at the permit desk.
|
Miscellaneous action | | | 6/25/2012 | | DONE |
|
|
|
denied plans taken to permit desk.
|
Plan resubmittals received | | | 6/18/2012 | | DONE |
Christina Prado
|
|
|
Received two revised sets of plans; small docs; applications and one new checklist. Gave to Stephanie for additional review
|
Alarm Plan Check | 6/15/2012 | | 6/15/2012 | | FAIL |
Stephanie L. Cobbley
|
|
|
Plans denied - see redlines and review comments.
|
Miscellaneous action | | | 6/15/2012 | | DONE |
|
|
|
Email sent to contractor letting him know the plans are denied and he can pick the redlines and review comments up from the permit desk.
|
Miscellaneous action | | | 6/15/2012 | | DONE |
|
|
|
Placed denied plans in the drawer at the permit counter.
|
1st review completed | | | 6/12/2012 | | FAIL |
|
|
|
Plans denied - no review done due to administrative holds.
|
Miscellaneous action | | | 6/12/2012 | | DONE |
|
|
|
Emailed Vanguard to let them know the early start request is denied.
|
Miscellaneous action | | | 6/12/2012 | | DONE |
|
|
|
Emailed Vanguard to let them know the review would not be completed due to administrative holds on the account.
|
Miscellaneous action | | | 6/12/2012 | | DONE |
|
|
|
Plans back in review status.
|
Application received | | | 6/11/2012 | | |
|
|
|
|