Permit Information
Permit NumberFIR12-00298
StatusFinaled
Name MOUNTAIN ALARM
Site Address 7000 W STATE ST
Project NameGoodwill Easter Seal
Customer Number 
ePlanReviewNo
Description
8/3/12 Plan Modification (4 devices affected): This plan modification is to incorporate field modifications (including a different FACP model number than previously submitted), add monitoring for an anti-freeze loop tamper switch, and to address previous review comments.
6/21/12: This fire alarm permit is to provide a manual fire alarm system in an existing building. This permit scope of work includes full notification, a manual pull station, smoke detector above the panels, smoke detectors for releasing a roll-up fire door, a remote power supply, two remote annunciator panels (one required at the main entrance, and one customer requested in an office), sprinkler system monitoring, and HVAC shutdown/monitoring.
Associated building permit: BLD12-00451
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  9/26/2012 DONE
Plans taken to records for scanning.
INSP-Final Inspection8/6/20128/7/20128/7/2012APASS
DetailsTroy Cobbley
Permit finaled
CHANGE STATUS TO (ISS)  8/6/2012 DONE
DetailsTisha Gallop
Plan assigned to (Stephanie)7/24/2012 8/3/2012 DONE
DetailsStephanie L. Cobbley
Miscellaneous action  8/3/2012 DONE
I emailed Mountain Alarm requesting a new device compatibility sheet. The one they provided is for the previously submitted fire alarm panel. I explained I need a new sheet that is for the actual panel installed.
Miscellaneous action  8/3/2012 DONE
Received requested documentation
Alarm Plan Check8/3/2012 8/3/2012 PASS
DetailsStephanie L. Cobbley
Plan modification approved with redlines and review comments.
PLANS TAKEN FRONT DESK ALARM  8/3/2012 DONE
Approved plan modification taken to permit technician for processing.
Inspection Record Card- Fire8/3/2012 8/3/2012 DONE
DetailsDarla L Downs
Permit Ready to Issue  8/3/2012  
Telephone call  8/3/2012  
8-3-12 called Mountain Alarm- Brett A. permit ready and fee given ///dld
INSP-Final Inspection7/23/20127/24/20127/24/2012AFAIL
DetailsTroy Cobbley
Plan modifications need to be submitted showing the different model of facp installed, device address changes, additional tamper switches in the riser room and the addtional antifreeze loop (tamper switch) at teh front canopy. The plan modification needs to include revised EOL drops due to needing to increase the candellas of several strobes due to addtional strobes, overspacing of strobes shown and the need to increase the 15cd strobes to 30cd because the ceiling heights in the corridor exceeded their 10' maximum listing height. Secondary phone line programmed to be recognized as I waited. The smoke detector over the facp activated without being tested and while covered at the beginning of the inspection but did not give an un-announced repeat performance.
Plan resubmittals received  7/24/2012 DONE
rec'd two copies
Issue and Print Permit  6/22/2012 DONE
DetailsBarbara Stitt
Plan assigned to (Stephanie)6/13/2012 6/21/2012 DONE
DetailsStephanie L. Cobbley
1st review completed  6/21/2012 PASS
Alarm Plan Check6/21/2012 6/21/2012 PASS
DetailsStephanie L. Cobbley
Plans approved with redlines and review comments.
PLANS TAKEN FRONT DESK ALARM  6/21/2012 DONE
Approved redlined plans available at front counter.
Permit Ready to Issue  6/21/2012  
Telephone call  6/21/2012  
6-21-12 called Mountain Alarm permit ready and fee given ///dld
Inspection Record Card- Fire6/21/2012 6/21/2012 DONE
DetailsDarla L Downs
Application received  6/13/2012