Miscellaneous action | | | 9/26/2012 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 8/6/2012 | 8/7/2012 | 8/7/2012 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
CHANGE STATUS TO (ISS) | | | 8/6/2012 | | DONE |
Tisha Gallop
|
|
|
|
Plan assigned to (Stephanie) | 7/24/2012 | | 8/3/2012 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Miscellaneous action | | | 8/3/2012 | | DONE |
|
|
|
I emailed Mountain Alarm requesting a new device compatibility sheet. The one they provided is for the previously submitted fire alarm panel. I explained I need a new sheet that is for the actual panel installed.
|
Miscellaneous action | | | 8/3/2012 | | DONE |
|
|
|
Received requested documentation
|
Alarm Plan Check | 8/3/2012 | | 8/3/2012 | | PASS |
Stephanie L. Cobbley
|
|
|
Plan modification approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 8/3/2012 | | DONE |
|
|
|
Approved plan modification taken to permit technician for processing.
|
Inspection Record Card- Fire | 8/3/2012 | | 8/3/2012 | | DONE |
Darla L Downs
|
|
|
|
Permit Ready to Issue | | | 8/3/2012 | | |
|
|
|
|
Telephone call | | | 8/3/2012 | | |
|
|
|
8-3-12 called Mountain Alarm- Brett A. permit ready and fee given ///dld
|
INSP-Final Inspection | 7/23/2012 | 7/24/2012 | 7/24/2012 | A | FAIL |
Troy Cobbley
|
|
|
Plan modifications need to be submitted showing the different model of facp installed, device address changes, additional tamper switches in the riser room and the addtional antifreeze loop (tamper switch) at teh front canopy. The plan modification needs to include revised EOL drops due to needing to increase the candellas of several strobes due to addtional strobes, overspacing of strobes shown and the need to increase the 15cd strobes to 30cd because the ceiling heights in the corridor exceeded their 10' maximum listing height. Secondary phone line programmed to be recognized as I waited. The smoke detector over the facp activated without being tested and while covered at the beginning of the inspection but did not give an un-announced repeat performance.
|
Plan resubmittals received | | | 7/24/2012 | | DONE |
|
|
|
rec'd two copies
|
Issue and Print Permit | | | 6/22/2012 | | DONE |
Barbara Stitt
|
|
|
|
Plan assigned to (Stephanie) | 6/13/2012 | | 6/21/2012 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 6/21/2012 | | PASS |
|
|
|
|
Alarm Plan Check | 6/21/2012 | | 6/21/2012 | | PASS |
Stephanie L. Cobbley
|
|
|
Plans approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 6/21/2012 | | DONE |
|
|
|
Approved redlined plans available at front counter.
|
Permit Ready to Issue | | | 6/21/2012 | | |
|
|
|
|
Telephone call | | | 6/21/2012 | | |
|
|
|
6-21-12 called Mountain Alarm permit ready and fee given ///dld
|
Inspection Record Card- Fire | 6/21/2012 | | 6/21/2012 | | DONE |
Darla L Downs
|
|
|
|
Application received | | | 6/13/2012 | | |
|
|
|
|