Information based on query as of Friday, August 16, 2024.
Permit Information
Permit NumberFIR12-00315
StatusFinaled
Name DELTA FIRE SYSTEMS
Site Address 357 N STEELHEAD WAY
Project NameSCP Sales Center 186
Customer Number 
ePlanReviewNo
Description
The fire sprinkler scope of work consists of relocating sprinklers in an existing office area. The warehouse area is not included in this review. The existing system is a 4”x4”x1½” grid with a 6” center rail. The original hydraulic calculations were reported as .30/3100 + 500 hose. Therefore, new hydraulic calculations for the light hazard area were not necessary. The reported flow information is S-84, R-40, Q-2000. The original demand was 968 Gpm @ 59 Psi

The storage is approved for a maximum of 15' high see BLD12-01043 fire safety review report
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  10/11/2012 DONE
DetailsTim Frost
Sent to Records for scanning.
INSP-Final Inspection7/20/20127/20/20127/20/2012PPASS
DetailsTroy Cobbley
Permit finaled
Plan resubmittals received  7/20/2012 DONE
Received updated owners certificate and HMIS.
INSP-Sprinkler Rough-in7/18/20127/18/20127/18/2012PPASS
DetailsTroy Cobbley
Sprinkler piping in the office area can be covered. A revised "Owners Certificate" will be required prior to a final sign off addressing the actual storage heigth.
Issue and Print Permit  6/27/2012 DONE
Plan assigned to (Tim)6/15/2012 6/26/2012 DONE
DetailsTim Frost
Sprinkler Plan Check6/26/2012 6/26/2012 PASS
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
PLANS/APPL TAKEN TO FRONT DESK  6/26/2012 DONE
DetailsTim Frost
Inspection Record Card- Fire6/26/2012 6/26/2012 DONE
DetailsDarla L Downs
Permit Ready to Issue  6/26/2012  
Telephone call  6/26/2012  
6-26-12 called Mick - Delta Fire Systems permit ready and fee given ///dld
Plan resubmittals received  6/21/2012 DONE
DetailsChristina Prado
Received three new sets of apps; checklists; plans; united water flow sheet; calcs and response letters. Gave to Tim Frost for further review
Sprinkler Plan Check6/19/2012 6/19/2012 FAIL
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
1st review completed  6/19/2012 FAIL
DetailsTim Frost
Miscellaneous action  6/19/2012 DONE
DetailsTim Frost
Emailed review to contractor
Telephone call  6/19/2012  
6-19-12 called Delta Fire permit ready for pick up ///dld
Application received  6/15/2012