Miscellaneous action | | | 4/16/2013 | | DONE |
|
|
|
Plans taken to records for scanning
|
INSP-Final Inspection | 3/5/2013 | 3/6/2013 | 3/6/2013 | A | PASS |
Forrest France
|
|
|
C/N items verified. Record of completion forms recieved. Fire alarm permit finaled.
|
INSP-Final Inspection | 12/28/2012 | 12/28/2012 | 12/28/2012 | P | FAIL |
Troy Cobbley
|
|
|
Will be able to final when the call list has been set up and the NFPA 72 are complete.
|
INSP-Final Inspection | 12/26/2012 | 12/27/2012 | 12/27/2012 | A | FAIL |
Troy Cobbley
|
|
|
Signals were not received correctly at the monitoring station. Need NFPA 72 record of completion forms.
|
INSP-Final Inspection | 12/18/2012 | 12/19/2012 | 12/19/2012 | A | FAIL |
Troy Cobbley
|
|
|
No city approved drawings on site for review. I noted that the singel horn/strobe is mounted too high. Could not verify candella.
|
FIR-Aging Inspection | 11/19/2012 | 11/19/2012 | 11/20/2012 | | DEFR |
Troy Cobbley
|
|
|
Need site inspection request
|
Issue and Print Permit | | | 7/11/2012 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 6/22/2012 | | 7/9/2012 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Plan assigned to (Stephanie) | 6/22/2012 | | 7/9/2012 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 7/9/2012 | | PASS |
|
|
|
|
Alarm Plan Check | 7/9/2012 | | 7/9/2012 | | PASS |
Stephanie L. Cobbley
|
|
|
Plans approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 7/9/2012 | | DONE |
|
|
|
Approved redlined plans taken to permit technician for processing.
|
Inspection Record Card- Fire | 7/9/2012 | | 7/9/2012 | | DONE |
Darla L Downs
|
|
|
|
Permit Ready to Issue | | | 7/9/2012 | | |
|
|
|
|
Telephone call | | | 7/9/2012 | | |
|
|
|
7-9-12 called Dante- Simplex Grinnell permit ready and fee given ///dld
|
Application received | | | 6/22/2012 | | |
|
|
|
|