Miscellaneous action | | | 11/30/2012 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 11/29/2012 | 11/29/2012 | 11/29/2012 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
Miscellaneous action | | | 11/28/2012 | | DONE |
|
|
|
Contractor brought in a plan that showed the location of surrounding existing pull stations. I was able to verify that be eliminating the pull station there is still less than 200' travel distance to the next pull station. I told Adam with SimplexGrinnell to ensure that plan was part of the as-built drawings and that I approve of eliminating the pull station with address M1-112.
|
Telephone call | | | 11/27/2012 | | DONE |
|
|
|
Dante with SimplexGrinnell called. He said the engineer sent them an RFI to remove a pull station on the plans (specifically the one with address M1-112) and wanted to know if they could show that on as-builts rather than a plan modification. After looking at the plans, I explained to Dante that I can't approve the removal of the pull station without seeing where all of the other pull station locations are (these submittals only have partial floorplans for the scope of work area). Although the pull station in question is not at an exit, it may have been there because code requires no more than 200' travel distance to any pull station. Without knowing where the other pull stations are located, this can not be verified. I told him he could get me a single sheet at 1/8"=1'-0" scale showing the rest of the building and the pull stations. Once I verify the pull station can be eliminated, then I told him as-built drawings could be accepted, but I want to be able to verify code requirements have been met. He said he would get that to me right away.
|
INSP-Final Inspection | 11/20/2012 | 11/26/2012 | 11/26/2012 | A | FAIL |
Troy Cobbley
|
|
|
All items tested ok. Need resubmittals addressing the manual pull station that was deleted in the field.
|
FIR-Aging Inspection | 11/12/2012 | 11/12/2012 | 11/20/2012 | | NR |
Troy Cobbley
|
|
|
work is in progress
|
Issue and Print Permit | | | 8/13/2012 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 7/2/2012 | | 8/10/2012 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | 8/10/2012 | | 8/10/2012 | | PASS |
Stephanie L. Cobbley
|
|
|
Resubmittals approved with review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 8/10/2012 | | DONE |
|
|
|
Approved resubmittals taken to permit technician for processing.
|
Permit Ready to Issue | | | 8/10/2012 | | DONE |
Tisha Gallop
|
|
|
|
Inspection Record Card- Fire | 8/10/2012 | | 8/10/2012 | | DONE |
Tisha Gallop
|
|
|
|
Telephone call | | | 8/10/2012 | | DONE |
Tisha Gallop
|
|
|
called Simplex and told Tara permit is ready and fee
|
Plan resubmittals received | | | 8/6/2012 | | DONE |
Tisha Gallop
|
|
|
received two copies of application, submittal folder and plans; routed to Fire review.
|
Miscellaneous action | | | 7/18/2012 | | DONE |
|
|
|
Fire alarm contractor emailed to let them know the plans have been denied and that they can pick up the redlined plans and review comments at the permit desk.
|
Miscellaneous action | | | 7/18/2012 | | DONE |
|
|
|
denied redlined plans and review comments taken to permit counter.
|
1st review completed | | | 7/17/2012 | | FAIL |
|
|
|
|
Alarm Plan Check | 7/17/2012 | | 7/17/2012 | | FAIL |
Stephanie L. Cobbley
|
|
|
Plans denied - see redlines and review comments.
|
Application received | | | 7/2/2012 | | |
|
|
|
|