Permit Information
Permit NumberFIR12-00349
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 8055 W GODDARD RD
Project NameCAPITAL HIGH SCHOOL
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to extend the existing fire alarm system in to the new stairways, entrances, corridors etc… modified due to the tenant remodel. This scope of work includes notification, pull stations, and a duct detector.

Associated building permit: BLD12-00364
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  11/30/2012 DONE
Plans taken to records for scanning.
INSP-Final Inspection11/29/201211/29/201211/29/2012PPASS
DetailsTroy Cobbley
Permit finaled
Miscellaneous action  11/28/2012 DONE
Contractor brought in a plan that showed the location of surrounding existing pull stations. I was able to verify that be eliminating the pull station there is still less than 200' travel distance to the next pull station. I told Adam with SimplexGrinnell to ensure that plan was part of the as-built drawings and that I approve of eliminating the pull station with address M1-112.
Telephone call  11/27/2012 DONE
Dante with SimplexGrinnell called. He said the engineer sent them an RFI to remove a pull station on the plans (specifically the one with address M1-112) and wanted to know if they could show that on as-builts rather than a plan modification. After looking at the plans, I explained to Dante that I can't approve the removal of the pull station without seeing where all of the other pull station locations are (these submittals only have partial floorplans for the scope of work area). Although the pull station in question is not at an exit, it may have been there because code requires no more than 200' travel distance to any pull station. Without knowing where the other pull stations are located, this can not be verified. I told him he could get me a single sheet at 1/8"=1'-0" scale showing the rest of the building and the pull stations. Once I verify the pull station can be eliminated, then I told him as-built drawings could be accepted, but I want to be able to verify code requirements have been met. He said he would get that to me right away.
INSP-Final Inspection11/20/201211/26/201211/26/2012AFAIL
DetailsTroy Cobbley
All items tested ok. Need resubmittals addressing the manual pull station that was deleted in the field.
FIR-Aging Inspection11/12/201211/12/201211/20/2012 NR
DetailsTroy Cobbley
work is in progress
Issue and Print Permit  8/13/2012 DONE
Plan assigned to (Stephanie)7/2/2012 8/10/2012 DONE
DetailsStephanie L. Cobbley
Alarm Plan Check8/10/2012 8/10/2012 PASS
DetailsStephanie L. Cobbley
Resubmittals approved with review comments.
PLANS TAKEN FRONT DESK ALARM  8/10/2012 DONE
Approved resubmittals taken to permit technician for processing.
Permit Ready to Issue  8/10/2012 DONE
DetailsTisha Gallop
Inspection Record Card- Fire8/10/2012 8/10/2012 DONE
DetailsTisha Gallop
Telephone call  8/10/2012 DONE
DetailsTisha Gallop
called Simplex and told Tara permit is ready and fee
Plan resubmittals received  8/6/2012 DONE
DetailsTisha Gallop
received two copies of application, submittal folder and plans; routed to Fire review.
Miscellaneous action  7/18/2012 DONE
Fire alarm contractor emailed to let them know the plans have been denied and that they can pick up the redlined plans and review comments at the permit desk.
Miscellaneous action  7/18/2012 DONE
denied redlined plans and review comments taken to permit counter.
1st review completed  7/17/2012 FAIL
Alarm Plan Check7/17/2012 7/17/2012 FAIL
DetailsStephanie L. Cobbley
Plans denied - see redlines and review comments.
Application received  7/2/2012